Instruction manual –AQ F210 Feeder Protection IED
23 (292
)
Object open- and close signals of an object are connected to physical output relays.
Separate timeouts for objects are set in Settings menu. Synchronization wait- and Object
Ready wait timeouts are settable between 0.02…500.00 s (default 200ms, step 20ms). If
time expires the controlling of object fails. Same time settings apply with Maximum close-
and open command pulse lengths. Control Termination Timeout is set to 10 seconds as
default. After the set delay if the controlled object does not respond accordingly the
procedure is terminated and there will be fail message.
Access level for MIMIC control is selected between User, Operator, Configurator and
Super user. To control MIMIC the terms of user access level (password) has to be fulfilled.
As default the access level is set to Configurator.
For object local and remote controlling digital inputs can be used. Remote controlling via
bus is configured in protocol level.
Figure 3.2.2.3-20 Object output- and block signal setting.
Object statuses can be connected directly to physical outputs in Signal Connections menu
which is sub-menu to APP CONTR menu. It is possible to connect to output relay or to start-