Figure. 6.2.2 - 17. Operating mode "Trip".
6.2.3 Binary input functions
Table. 6.2.3 - 27. Binary input functions of AQ-1000.
Binary
Binary
input
input
LED name
LED name
FFunction
unction
Binary
input 1
Clear
Clears and resets the LED indications after an error or a trip event.
Binary
input 2
Commissioning When the device is in Commissioning mode, it can be tripped any number of times.
Binary
input 3
(N/A)
Not in use (reserved for future use).
Binary
input 4
Blocked
Blocks the activation of the trip contact during commissioning tests or during any other
circumstances where actual tripping must be prevented.
6.2.4 SET button
AQ-1000 contains contains a SET button in the front panel of the device. It is used for resetting the
LED indicators and for clearing the alarm signals.
A
AQ 100 (Siemens)
Q 100 (Siemens)
Instruction manual