background image

INSTALLATION INSTRUCTIONS

Apartment Fan Coil: FSA

664 01 5001 00

5

Refrigerant Lines
NOTE

: Do not remove seals from coil until tubing

connections are ready to be made. See instructions

packaged with outdoor unit for connecting refrigerant

tubes.

Move Fan Coil into place and install refrigerant tubing as

follows:

1. Route tubing to connection points.
2. Remove plugs from liquid and suction tubes.
3. Clean tubing and braze in place.
4. Pressurize system and leak test. Repeat

procedure until leak free.

ELECTRICAL CONNECTIONS

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) disconnect

device before working on incoming (field) wiring

could result in personal injury or death.
Incoming (field) wires on the line side of the dis-

connect found in the fan coil unit remain live, even

when the pull--out is removed. Service and main-

tenance to incoming (field) wiring cannot be safely

performed until the main disconnect switch (re-

mote to the unit) is turned off.

NOTE:

Before proceeding with electrical connections,

make certain that voltage, frequency, and phase

correspond to that specified on rating plate. Also, check to

be sure that the service provided by utility is sufficient to

handle additional load imposed by this equipment. Refer

to unit wiring label for proper field high--voltage and

low--voltage wiring. Make all electrical connections in

accordance with NEC and any local codes or ordinances

that might apply. Fan Coil must have a separate branch

electrical circuit. The Cooling Control Kit and the heater

packages provide a disconnect switch located within sight

and readily accessible to the unit.

NOTE:

All control kits are shipped from factory wired for

230V transformer operation. When 208V transformer

operation is required, move the black primary lead from

the 230V terminal to the 208V terminal.
Refer to Figure 1 for location of the electrical inlets. Refer

to unit rating plate for minimum circuit ampacity (MCA)

and maximum fuse or circuit breaker (maximum

over--current protection -- MOCP).

1. Provide power supply for Fan Coil in accordance

with unit wiring diagram and rating plate.

2. Connect line--voltage leads to field lugs. Use

copper wire only.

3. Use UL listed conduit and conduit connector for

connecting line--voltage leads to unit and obtaining

proper

ground.

Grounding

can

also

be

accomplished by using the ground lug provided in

the control box.

4. Install rubber grommet packed with unit in hole for

low--voltage wires.

5. Connect low--voltage leads to thermostat and

outdoor unit. Refer to Figures 4 and 5 and the

outdoor unit wiring label.

Use No. 18 AWG color--coded, insulated (35

˚

C

minimum) wire to make low--voltage connections

between thermostat and Fan Coil. If thermostat is located

more than 100 feet from Fan Coil as measured along

low--voltage wire, use No. 16 AWG color--coded,

insulated (35

˚

C minimum) wire. All control kits from the

factory utilize a printed--circuit board (PCB) which has a

low voltage circuit protective fuse (5 amp), fan motor

speed tap selection terminal (SPT), and time delay relay

(TDR) jumper. To disable the TDR feature, sever the

jumper wire JW1.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken

ground could result in personal injury or death.
According to NEC, ANSI/NFPA 70, and local

codes, the cabinet must have an uninterrupted or

unbroken ground in order to minimize potential

for personal injury or death if an electrical fault

should occur. The ground may consist of electri-

cal wire or metal conduit when installed in accor-

dance with existing electrical codes. If conduit

connection uses reducing washers, a separate

ground wire must be used.

Summary of Contents for FSA2X

Page 1: ...uals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Introduction 2 Check Equipment 2 Location 2 In...

Page 2: ...talled make sure adequate clearance is maintained from supply duct work See Clearances in Figure 1 If the Fan Coil is located in an area of high humidity nuisance sweating of casing may occur On these installations a wrap of 2 fiberglass insulation with a vapor barrier is recommended An access panel is provided on the front of the cabinet for simple access to blower assembly and electrical control...

Page 3: ...ply Duct 0 From Front for Service 21 With Heaters All Sides 0 From First 3 feet of Supply Duct to Combustibles 1 From Supply Duct after 3 feet 0 From Front for Service 21 CLEARANCES DIMENSIONAL DATA Model Size A B C D FSA2X FSA4X 18 153 16 81 4 23 4 381 16 24 153 16 81 4 23 4 381 16 30 153 16 81 4 23 4 381 16 36 183 8 91 4 5 433 16 ...

Page 4: ...ed on unit rating plate Do not use plastic lined or combus tible flexible ducting within 36 inchesof thesupply end of the fan coil Condensate Drain Condensate pan has primary and secondary drain connections to meet FHA requirements refer to Figure 3 These connections have 3 4 female pipe threads NPT Tubing for all condensate drains should be a minimum of 7 8 OD Drain lines from condensate pan to e...

Page 5: ... transformer operation is required move the black primary lead from the 230V terminal to the 208V terminal Refer to Figure 1 for location of the electrical inlets Refer to unit rating plate for minimum circuit ampacity MCA and maximum fuse or circuit breaker maximum over current protection MOCP 1 Provide power supply for Fan Coil in accordance with unit wiring diagram and rating plate 2 Connect li...

Page 6: ...ling control panel above blower motor on blower side plate Attach with provided screws 3 Route thermostat leads through small knockout in top of unit Use grommet provided with cooling control to protect leads where they pass through casing 4 Make low voltage splice connections in low voltage control box 5 Route blower motor power leads up through hole in bottom of cooling control Connect yellow co...

Page 7: ... service technician Consult the servicing dealer for recommended frequency Between visits the only consumer service recommended or required is air filter maintenance and condensate drain operation Air Filter Inspect air filters at least monthly and replace or clean as required Disposable type filters should be replaced Reusable type filters may be cleaned by soaking in mild detergent and rinsing w...

Reviews: