Arcoaire FSA2X Installation Instructions Manual Download Page 7

INSTALLATION INSTRUCTIONS

Apartment Fan Coil: FSA

664 01 5001 00

7

MOTOR SPEED SELECTION

Before operating Fan Coil, be sure that proper blower

speed has been selected. High speed tap is

recommended for most applications. For those

applications requiring lower air flows, low speed tap can

be used.

Color Code For Motor Lead Wires
MOTOR SPEED TAP

WIRE COLOR

C -- Common

Yellow

1 -- High

Black

2 -- Low

Red

NOTE:

Fan speeds are selected manually. To change the

fan speed, switch the black and red fan motor leads on

printed circuit board terminal SPT (COM).

START--UP PROCEDURE

Refer to outdoor unit Installation Instructions for system

start--up instructions and refrigerant charging method

details.

CARE AND MAINTENANCE

The system should be regularly inspected by a qualified

service technician. Consult the servicing dealer for

recommended frequency.
Between visits, the only consumer service recommended

or required is air filter maintenance and condensate drain

operation.

Air Filter

Inspect air filters at least monthly and replace or clean as

required. Disposable type filters should be replaced.

Reusable type filters may be cleaned by soaking in mild

detergent and rinsing with cold water. Install filters with

the arrows on the side pointing in the direction of air flow.

Condensate Drain

During the cooling season check at least monthly for free

flow of drainage and clean if necessary.

!

CAUTION

PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor

unit performance and/or product damage.
Never operate Fan Coil without a filter. Damage to

blower motor or coil may result. Factory autho-

rized filter kits must be used when locating the fil-

ter inside the unit.

International Comfort Products, LLC

Lewisburg, TN 37091

Summary of Contents for FSA2X

Page 1: ...uals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Introduction 2 Check Equipment 2 Location 2 In...

Page 2: ...talled make sure adequate clearance is maintained from supply duct work See Clearances in Figure 1 If the Fan Coil is located in an area of high humidity nuisance sweating of casing may occur On these installations a wrap of 2 fiberglass insulation with a vapor barrier is recommended An access panel is provided on the front of the cabinet for simple access to blower assembly and electrical control...

Page 3: ...ply Duct 0 From Front for Service 21 With Heaters All Sides 0 From First 3 feet of Supply Duct to Combustibles 1 From Supply Duct after 3 feet 0 From Front for Service 21 CLEARANCES DIMENSIONAL DATA Model Size A B C D FSA2X FSA4X 18 153 16 81 4 23 4 381 16 24 153 16 81 4 23 4 381 16 30 153 16 81 4 23 4 381 16 36 183 8 91 4 5 433 16 ...

Page 4: ...ed on unit rating plate Do not use plastic lined or combus tible flexible ducting within 36 inchesof thesupply end of the fan coil Condensate Drain Condensate pan has primary and secondary drain connections to meet FHA requirements refer to Figure 3 These connections have 3 4 female pipe threads NPT Tubing for all condensate drains should be a minimum of 7 8 OD Drain lines from condensate pan to e...

Page 5: ... transformer operation is required move the black primary lead from the 230V terminal to the 208V terminal Refer to Figure 1 for location of the electrical inlets Refer to unit rating plate for minimum circuit ampacity MCA and maximum fuse or circuit breaker maximum over current protection MOCP 1 Provide power supply for Fan Coil in accordance with unit wiring diagram and rating plate 2 Connect li...

Page 6: ...ling control panel above blower motor on blower side plate Attach with provided screws 3 Route thermostat leads through small knockout in top of unit Use grommet provided with cooling control to protect leads where they pass through casing 4 Make low voltage splice connections in low voltage control box 5 Route blower motor power leads up through hole in bottom of cooling control Connect yellow co...

Page 7: ... service technician Consult the servicing dealer for recommended frequency Between visits the only consumer service recommended or required is air filter maintenance and condensate drain operation Air Filter Inspect air filters at least monthly and replace or clean as required Disposable type filters should be replaced Reusable type filters may be cleaned by soaking in mild detergent and rinsing w...

Reviews: