INSTALLATION INSTRUCTIONS

Apartment Fan Coil: FSA

664 01 5001 00

3

Figure 1

Clearances and Dimensions

No Heaters

All Sides

0"

From Supply Duct

0"

From Front (for Service)

21"

With Heaters

All Sides

0"

From First 3 feet of Supply Duct to Combustibles

1"

From Supply Duct after 3 feet

0"

From Front (for Service)

21"

CLEARANCES

DIMENSIONAL DATA

Model Size

A

B

C

D

FSA2X
FSA4X

18

15

3/16

8

1/4

2

3/4

38

1/16

24

15

3/16

8

1/4

2

3/4

38

1/16

30

15

3/16

8

1/4

2

3/4

38

1/16

36

18

3/8

9

1/4

5

43

3/16

Summary of Contents for FSA2X

Page 1: ...uals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Introduction 2 Check Equipment 2 Location 2 In...

Page 2: ...talled make sure adequate clearance is maintained from supply duct work See Clearances in Figure 1 If the Fan Coil is located in an area of high humidity nuisance sweating of casing may occur On these installations a wrap of 2 fiberglass insulation with a vapor barrier is recommended An access panel is provided on the front of the cabinet for simple access to blower assembly and electrical control...

Page 3: ...ply Duct 0 From Front for Service 21 With Heaters All Sides 0 From First 3 feet of Supply Duct to Combustibles 1 From Supply Duct after 3 feet 0 From Front for Service 21 CLEARANCES DIMENSIONAL DATA Model Size A B C D FSA2X FSA4X 18 153 16 81 4 23 4 381 16 24 153 16 81 4 23 4 381 16 30 153 16 81 4 23 4 381 16 36 183 8 91 4 5 433 16 ...

Page 4: ...ed on unit rating plate Do not use plastic lined or combus tible flexible ducting within 36 inchesof thesupply end of the fan coil Condensate Drain Condensate pan has primary and secondary drain connections to meet FHA requirements refer to Figure 3 These connections have 3 4 female pipe threads NPT Tubing for all condensate drains should be a minimum of 7 8 OD Drain lines from condensate pan to e...

Page 5: ... transformer operation is required move the black primary lead from the 230V terminal to the 208V terminal Refer to Figure 1 for location of the electrical inlets Refer to unit rating plate for minimum circuit ampacity MCA and maximum fuse or circuit breaker maximum over current protection MOCP 1 Provide power supply for Fan Coil in accordance with unit wiring diagram and rating plate 2 Connect li...

Page 6: ...ling control panel above blower motor on blower side plate Attach with provided screws 3 Route thermostat leads through small knockout in top of unit Use grommet provided with cooling control to protect leads where they pass through casing 4 Make low voltage splice connections in low voltage control box 5 Route blower motor power leads up through hole in bottom of cooling control Connect yellow co...

Page 7: ... service technician Consult the servicing dealer for recommended frequency Between visits the only consumer service recommended or required is air filter maintenance and condensate drain operation Air Filter Inspect air filters at least monthly and replace or clean as required Disposable type filters should be replaced Reusable type filters may be cleaned by soaking in mild detergent and rinsing w...