24

English

Air Curtain must never be used by children or unfit per

-

sons without supervision.

This appliance is intended to be used by expert or trai

-

ned users in shops, in light industry and on farms, or for 

commercial use by lay persons.
It is dangerous to touch the unit with damp parts of the 

body and bare feet.
Always unplug the unit from the mains power supply 

before carrying out any type of operation or mainte-

nance.
Never tamper with or modify regulation and safety devi-

ces without prior authorisation and instructions.
Never twist, detach or pull power cables, even when 

the unit is unplugged from the mains power supply.
Never throw or spray water on the unit.
Never introduce foreign objects through the air intake 

and discharge grids.

Never remove protective elements without first unplug

-

ging the unit from the mains power supply.
Do not throw packaging material away or leave it with 

in reach of children as it may represent a hazard.

Do  not  install  in  explosive,  corrosive  or  damp  envi

-

ronments, outdoors or in very dusty rooms.

- FUNDAMENTAL  SAFETY  RULES

This appliance can be used by children aged from 8 

years and above and persons with reduced physical, 

sensory  or  mental  capabilities  or  lack  of  experience 

and knowledge if they have been given supervision or 

instruction concerning use of the appliance in a safe 

way and understand the hazards involved.
Children shall not play with the appliance. 
Cleaning and user maintenance shall not be made by 

children without supervision.
Before carrying out any operation on the appliance, 

make sure:
1 - The unit is disconnected from  the electrical power 

supply.
2 - The coil water supply valve is  closed and the coil 

has cooled  down 

(DCA-ECM-W)

.

3 - Install a safety switch to turn  off current to the 

appliance in  an easily accessible position  near the 

unit or units. 

- SAFETY  RULES

During installation, maintenance and repairs, for safety 

reasons, observe the following precautions:
• Always use work gloves. 
• 

Do not expose  to inflammable gas

• Do not place objects  over the grids.
Make sure the unit is earthed.
When moving the appliance, lift it by yourself (for weights 

of under 30 kg) or with the help of another person.
Lift it slowly, taking care not to drop it.
Fan blades may reach speeds ofup to 1300 revs/min. 

Never introduce objects or the hand into the fans.
Do not remove the safety labels inside the appliance.
If you cannot read the labels, ask for replacements.
Always use original spare parts.
In particularly cold climates, if the appliance is not to be 

used for long periods, drain the hydraulic circuit.

WARNING!

DANGEROUS VOLTAGE.

DON’T MAKE 

ANY OPERATION TYPE 

BEFORE THE VOLTAGE SWITCH OFF.

WAIT AT LEAST 3 MINUTES

Summary of Contents for DCA

Page 1: ...Luftschleier Einheit DCA ECM AKP 2019 05 Cod 4050577AR IT MANUALE DI INSTALLAZIONE E MANUTENZIONE EN INSTALLATION AND MAINTENANCE MANUAL DE INSTALLATIONS UND WARTUNGSANLEITUNG DCA ECM...

Page 2: ...ng the instructions contained in this manual you will be sure to appreciate the quality of our machine Please therefore carefully read the instructions of use contained in this manual which comply wit...

Page 3: ...nzione Operazioni particolarmente importanti e o pericolose Important Particularly important and or delicate operations Achtung Besonders wichtige und oder gef hrliche Arbeitsg nge Interventi che poss...

Page 4: ...po che le stesse abbiano ricevuto istruzioni relative all uso sicuro dell apparecchio e alla comprensione dei pericoli ad esso inerenti I bambini non devono giocare con l apparecchio La pulizia e la m...

Page 5: ...lla stessa visibile sulla targhetta di identificazione Il presente manuale rispecchia lo stato della tecnica al momento della sua redazione il fabbricante si riserva il diritto di aggiornare la produz...

Page 6: ...na volta che l apparecchio disinballato controllare che non vi siano danni e che corrisponda alla fornitura In caso di danni o di sigla dell apparecchio non corrispon dente a quanto ordinato rivolgers...

Page 7: ...Manuale nella documentazione tec nica a parte o nella proposta tecnica Le parti di consumo e quelle sostituite vanno smaltite nel rispetto della sicu rezza e in conformit con le norme di protezione a...

Page 8: ...Litri Grandezza 1 2 3 A 1144 1644 2150 B 774 1274 1274 DIMENSIONI mm Type Grandezza Unit non imballata 1 2 3 DCA ECM A 14 20 29 DCA ECM W 16 23 32 DCA ECM E 16 23 33 PESO kg Grandezza 1 2 3 230 1 50Hz...

Page 9: ...nit per otte nere il miglior rendimento di funzionamento ed evitare guasti o condizioni di pericolo deve avere i seguenti requisiti La barriera d aria dev essere montata orizzontalmente con la griglia...

Page 10: ...10 Italiano INSTALLAZIONE MECCANICA 35 150 B Mod B 10 774 1274 15 30 16 150 16 6 5 12 R6 6 5 1 2 3...

Page 11: ...dimensioni in Fig 1 E necessario conpensare le staffe per adattarle alla parete qualora quest ultima presenti una superficie irre golare Agganciare l unit al bordo inferiore della staffe Fig 3 Innesta...

Page 12: ...mentazione elettrica prima di accedere alla macchina Controllare che il cavo di alimentazione sia in perfetto stato In nessun caso si deve riparare il cavo eventualmente danneggiato con nastro isolant...

Page 13: ...CM E 230 Vac Allacciare il cavo di alimentazione alla linea elettrica mediante la spina 230Vac 50 Hz Versioni DCA ECM E 400 Vac Allacciare il cavo di alimentazione alla linea elettrica mediante la spi...

Page 14: ...N OUT E U Il lavoro deve essere eseguito da un installatore autorizzato IN OUT E U UTILIZZARE ATTUATORI ON OFF 230VAC 50HZ Le Lame d aria DCA ECM W sono dotate di un controllo elettronico predisposto...

Page 15: ...Italiano 15 COLLEGAMENTO ELETTRICO ATTUATORE VALVOLA 3 2 1 1 2 5 3 4 6 7 8 9 DCA ECM W...

Page 16: ...di ripristino come da immagine che segue In caso di intervento della protezione a riarmo manuale occorrer ripristinare il sistema solo dopo aver tolto ten sione ed aver accertato la causa di guasto i...

Page 17: ...contatto porta SCHEDA ELETTRONICA DEL COMANDO IN1 ON 1 2 3 4 IN2 DSC DIP 5 6 J1 MC3 LEGENDA DIP Dip Switch di configurazione IN2 Contatto Porta DSC IN1 ON OFF remoto Vedi JUMPER MC3 RS485 Seriale ver...

Page 18: ...r DIP 4 OFF Slave DIP 4 ON Slave DIP 4 ON ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND Master DIP 4 OFF Slave DIP 4 ON S...

Page 19: ...ficare i parametri di funzio namento del ventilconvettore occorre inviare le istru zioni premendo il tasto ON SEND BATTERIE Prima di effettuare qual siasi operazione con il telecomando inserire le bat...

Page 20: ...a 2 Trasferimento modalit di funzionamento Per inviare l informazione all apparecchio premere il tasto ON SEND Impostazione dell orologio del telecomando e o dell ap parecchio IMPOSTAZIONE DEL SET DES...

Page 21: ...ENTO C SET TEMP OFF Select Fan Mode On Send TIMER C SET TEMP OFF Select Fan Mode On Send TIMER Ventilazione Riscaldamento con On Off valvola DCA ECM W Riscaldamento con Potenza Max resistenza elettric...

Page 22: ...remere il tasto SELECT il simbolo del TIMER inizier a lampeggiare l impostazione TIMER sar quella selezionata in precedenza Ogni volta che si modifica l impostazione TIMER ON o OFF il simbolo di trasm...

Page 23: ...42090 DSC CONTATTO PORTA 1 11 5 65 78 88 9 2 6 5 4 7 25 13 Schema elettrico Dimensioni Indicazioni operative nero RISOLUZIONE DEI PROBLEMI Se i ventilatori non funzionano o non funzionano ade guatamen...

Page 24: ...dge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user ma...

Page 25: ...in addition the manual provides important information about mainte nance any residual risks and however how to carry out operations to be performed with special care This manual is to be considered a...

Page 26: ...ing After unpacking the appliance make sure it is undama ged and corresponds to the unit requested In the event of damage or if the identi cation code does not correspond to that ordered contact your...

Page 27: ...l in the separate techni cal documentation or in the technical proposal Consumables and replaced parts should be disposed of safely and in accordance with environmental protection legislation WASTE DI...

Page 28: ...TENTS Litres Model 1 2 3 A 1144 1644 2150 B 774 1274 1274 DIMENSIONS mm Type Model Unpacked unit 1 2 3 DCA ECM A 14 20 29 DCA ECM W 16 23 32 DCA ECM E 16 23 33 WEIGHT kg Model 1 2 3 230 1 50Hz Watt Ma...

Page 29: ...st performance and prevent breakdowns or hazards must have the following requisites The air curtain unit must be installed horizontally with the supply air grille facing downwards as close to the door...

Page 30: ...30 English MECHANICAL INSTALLATION 35 150 B Mod B 10 774 1274 15 30 16 150 16 6 5 12 R6 6 5 1 2 3...

Page 31: ...ll see Fig 2 and dimension drawing Fig 1 If the wall is uneven the brackets must be compensated for this Hook on the unit at the lower edge of the brackets Fig 3 Engage the top of the unit and tighten...

Page 32: ...ectrical power supply before opening the unit Check regularly that the power supply cable is undamaged Under no circumstance shall the electric power cable that may have been damaged be repaired with...

Page 33: ...50 Hz DCA ECM E Version 400 Vac Connect the power supply cable to the mains supply using a plug 230 Volt Connect the power cable supplied with the appropriate power of the dorsal 400Vac 50Hz 3P 230Va...

Page 34: ...l code 3021325 READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THE CONTROL HYDRAULIC CONNECTIONS MAXIMUM WORKING PRESSURE 1000 kPa ALWAYS USE TWO SPANNERS TO CONNECT THE HEAT EXCHANGER TO THE PIPES ALW...

Page 35: ...35 English VALVE ACTUATOR CONNECTION DIAGRAMS 3 2 1 1 2 5 3 4 6 7 8 9 DCA ECM W...

Page 36: ...rearming the position of the reset device is as shown in the gure In the event the manual rearm protective device inter venes the system will need to be restored only after having cut power and found...

Page 37: ...act closure Contact IN2 DSC Dorr Contact When the contact is open the appliance can operate When the contact is closed the appliance is stopped Function associated with the post ventilation See table...

Page 38: ...kink knot snag or fray when rolling it out or securing it ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND Master DIP 4 OFF...

Page 39: ...S Before performing any operations with the remote control insert the batteries supplied Type AAA 1 5 Volt batterie smust be used DISPOSE OF THE BATTERIES PROPERLY USING THE PROPER WASTE CONTAINERS IN...

Page 40: ...again to exit the procedure 2 Transferring the operating mode To send the information to the appliance press the ON SEND button Setting the clock on the remote control and or the appliance SETTING THE...

Page 41: ...RATING MODES C SET TEMP OFF Select Fan Mode On Send TIMER C SET TEMP OFF Select Fan Mode On Send TIMER Only Fan Heating with On Off val ve DCA ECM W Heating with maximum power of the Electrical resist...

Page 42: ...the and buttons Press the SELECT button the TIMER symbol will start flashing the TIMER settings will be those previously set Whenever the TIMER ON or OFF settings are modified the transmission symbols...

Page 43: ...W check also the following That the water coil is air free That there is enough water flow That incoming water is heated enough If the fault cannot be rectified please contact a qualified service tech...

Page 44: ...terwiesen wurden und die daraus resultierenden Gefahren verstanden haben Kinder d rfen nicht mit dem Ger t spielen Die Reinigung und die Benutzer Wartung d rfen nicht durch Kinder durchgef hrt werden...

Page 45: ...ise f r die Wartung eventuelle Restrisiken und ganz allgemein f r T tigkeiten die mit besonderer Vorsicht durchgef hrt werden m ssen Das vorliegende Handbuch ist als Teil der Maschine zu be trachten u...

Page 46: ...muss kontrolliert werden dass keine Besch digungen vorliegen und dass die Lieferung vollst ndig ist Wenn Besch digungen vorliegen oder wenn der Ger te code nicht mit dem bestellten Code bereinstimmt m...

Page 47: ...und die ausge tauschten Teile m ssen sicher und in bereinstimmung mit den Umwelt schutzvorschriften entsorgt werden ENTSORGUNG GEWICHTE UND ABMESSUNGEN VERPACKTES GER T Ger t und Steuerung Bedienungs...

Page 48: ...274 DIMENSIONEN mm Art Modell Unverpackten Ger ts 1 2 3 DCA ECM A 14 20 29 DCA ECM W 16 23 32 DCA ECM E 16 23 33 GEWICHT kg Modell 1 2 3 230 1 50Hz Watt Max A Max Watt Max A Max Watt Max A Max DCA ECM...

Page 49: ...zielung der besten Leistung und zur Vermeidung von St rungen oder Gefahrensituationen muss die Installati onsposition der Einheit folgende Anforderungen erf llen Die Barriere muss horizontal mit nach...

Page 50: ...50 Deutsch MECHANISCHE INSTALLATION 35 150 B Mod B 10 774 1274 15 30 16 150 16 6 5 12 R6 6 5 1 2 3...

Page 51: ...1 Sollte die Wand eine unregelm ige Oberfl che aufwei sen so m ssen die B gel kompensiert werden um sie an die Wand anzupassen Die Einheit in den unteren Rand der B gel einh ngen Abb 3 Den oberen Teil...

Page 52: ...tromversorgung getrennt werden Sicherstellen dass sich das Versorgungskabel in einem einwandfreien Zustand befindet In keinem Fall darf ein eventuell besch digtes Kabel mit Isolierband oder Klemmen re...

Page 53: ...CA ECM E 230 Vac Das Versorgungskabel ber den Stecker an die Stromleitung anschlie en 230 Vac 50 Hz Ausf hrungen DCA ECM E 400 Vac Das Versorgungskabel ber den Stecker an die Stromleitung 230 Volt ans...

Page 54: ...sierten Installateur vorgenommen werden IN OUT E U ON OFF ANTRIEBE 230 VAC 50 Hz VERWENDEN Die Luftschleier DCA ECM W sind mit einer vor eingestellten elektronischen Steuerung zur Durchf hrung untersc...

Page 55: ...55 Deutsch ELEKTROANSCHLUSS VENTILANTRIEB 3 2 1 1 2 5 3 4 6 7 8 9 DCA ECM W...

Page 56: ...le eines Eingriffs der Schutzvorrichtung mit manu eller R ckstellung kann das System erst r ckgestellt wer den nachdem die Spannung getrennt und die Ursache der St rung beseitigt wurde dieser Eingriff...

Page 57: ...TEUERPLATINE IN1 ON 1 2 3 4 IN2 DSC DIP 5 6 J1 MC3 LEGENDE DIP Konfigurations DIP Schalter IN2 T rkontakt DSC IN1 ON OFF extern siehe JUMPER MC3 RS485 Serielle Schnittstelle f r SLAVE Ger te J1 JUMPER...

Page 58: ...DIP 4 OFF Slave DIP 4 ON Slave DIP 4 ON ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 TX RX GND TX RX GND ON 1 2 3 4 DIP 5 6 MC3 TX RX GND TX RX GND Master DIP 4 OFF Slave DIP 4 ON Sl...

Page 59: ...onsparameter des Gebl sekonvektors ver ndert werden sollen m ssen die Befehle durch Dr cken der Taste ON SEND gesen BATTERIEN Vor Durchf hrung von T tigkeiten mit der Fern bedienung m ssen die mitgeli...

Page 60: ...mms dr cken 2 bertragung des Funktionsmodus Zur bermittlung der Information an das Ger t die Taste ON SEND dr cken Einstellung der Uhr der Fernbedienung und oder des Ger ts EINSTELLUNG DES GEW NSCHTEN...

Page 61: ...Taste ON SEND dr cken BETRIEBSMODUS C SET TEMP OFF Select Fan Mode On Send TIMER C SET TEMP OFF Select Fan Mode On Send TIMER Bel ftung Heizung mit On Off Ventil DCA ECM W Heizung mit max Leistung Hei...

Page 62: ...erwenden Die Taste SELECT dr cken das TIMER Symbol beginnt zu blinken Die Einstellung des TIMERS ent spricht der zuvor vorgenommenen Jedes Mal wenn die Einstellung TIMER ON oder OFF ver ndert wird bli...

Page 63: ...g der Komponente angef hrt werden ZUBEH RTEILE Code 9042090 DSC T RKONTAKT Blau Schwarz 1 11 5 65 78 88 9 2 6 5 4 7 25 13 Schaltplan Dimensionen Betriebsf hrung BEHEBUNG VON PROBLEMEN Wenn die Gebl se...

Page 64: ...Board E Hot water valve R Electrical Resistance T1 Air Probe Q1 Q2 Q3 Contactor B1 Safety Thermostat Manual Reset B2 B3 Safety Thermostat Automatic Reset In2 DSC Door Contact optional cod 9042090 In1...

Page 65: ...N N N N V2 V1 H20 EH1EH2 T1 N L 230V BU BN BU BN In1 In2 DSC RT03 3 M A 230V Inverter BLAC Board GNYE 10 0 50Hz L A GNYE N BK BU BU BK WH RD RD WH DIP6 ON DIP3 OFF Cod 3021235 DIP5 OFF Optional _ Fan...

Page 66: ...V2 V1 H20 EH1EH2 T1 N L 230V BU BN BU BN In1 In2 DSC 3 M A 230V Inverter BLAC Board GNYE 10 0 50Hz L A GNYE N BN BU BU BK WH RD RD WH DIP6 ON BU BK E BN BU DIP3 OFF DIP5 OFF RT03 Cod 3021235 Optional...

Page 67: ...IDSTHERMOSTAT B3 B3 Thermal cut Off 45 C Automatic Reset B1 Thermal cut Off 80 C Manual Reset R I BU DIP5 ON DIP3 OFF BK DIP6 ON WH RD RD WH BK BU BU GY N GNYE A L 50Hz 0 10 GNYE Inverter BLAC Board 2...

Page 68: ...RITE TERMOSTATO DE SEGURIDAD VEILIGHEIDSTHERMOSTAT B3 B3 Thermal cut Off 45 C Automatic Reset B1 Thermal cut Off 80 C Manual Reset BK N L T1 230Vac 50 Hz Power Board SELV Board N N N N V2 V1 H20 EH1EH...

Page 69: ...GURIDAD VEILIGHEIDSTHERMOSTAT B3 B3 Thermal cut Off 45 C Automatic Reset B1 Thermal cut Off 80 C Manual Reset BK N L T1 230Vac 50 Hz Power Board SELV Board N N N N V2 V1 H20 EH1EH2 T1 N L 230V BU BN B...

Page 70: ...70 T T 1 1 1 2 3 5 N L T1 T1 RT03 3 M 230V 50Hz L N Optional _ Fan M SELV Board 5 6 7 T MB DIP4 ON DIP3 ON DIP3 ON DIP5 ON DIP6 ON SE 0510 DCA ECM 3 E 400Vac...

Page 71: ...ther normative document s EN 60335 1 2012 A11 2014 EN 60335 2 40 2003 A11 2004 A12 2005 A1 2006 A2 2009 A13 2012 EN 60335 2 30 2011 A11 2013 EN 55014 1 2006 A1 2009 A2 2011 EN 55014 2 2015 EN 61000 3...

Page 72: ...fon 41 71 447 48 48 Fax 41 71 447 48 49 Email verkauf prolux ag ch Web www prolux ag ch Kermi Sp z o o Ul Granicna 8b 3 URF DZ T 48 71 35 40 370 F 48 71 35 40 463 www kermi pl 58 PDLO QIR DIJ UXV UX Z...

Reviews: