External Power Supply
Part number: AP0011200.
Type: +7 Vdc, regulated; 5 W
Measurements
Voltage and Current
Method:
True rms, 3 kHz Bandwidth
Accuracy:
0.1% of reading (voltage) or
±
5 mV,
whichever is greater
0.1% of reading (current) + CT errors
1% of r CT errors (low range)
Phase Angle, A to B
Range:
0 to 360 or
±
180
◦
Accuracy:
0.1
◦
underrange:
<
1
◦
, typical
Frequency
Range:
50 or 60 Hz
±
5 Hz
Accuracy:
0.005% of reading
Harmonics
Input:
Channel A and B, simultaneous
Range:
2nd to 50th (50 or 60 Hz fund.)
Accuracy:
0.1% THD + 5% reading
89
Summary of Contents for 928A
Page 1: ...MODEL 928A USER S MANUAL Arbiter Systems Inc Paso Robles CA 93446 U S A ...
Page 6: ...vi ...
Page 12: ...xii ...
Page 14: ...xiv ...
Page 57: ...Channel B Combined Caution For current probe use see CT Probe Use on page 4 43 ...
Page 112: ...CT Cable Connector Figure 16 CT Cable Connector side view Figure 17 CT Connector End View 98 ...
Page 114: ...100 ...
Page 115: ...CE Mark Certification ...