DEFAULT PARAMETER SETTINGS
Page 24
(1)
When the Hardness unit is changed, the Exchange capacity per liter resin needs to be adjusted accordingly; to convert from °f to °d, multiply x 0,56; 5,5 °f
M
3
/L equals 3,1 °d M
3
/L.
(2)
When the Exchange capacity per liter resin is changed, the refill cycle time needs to be adjusted accordingly.
(1)
When the Hardness unit is changed, the Exchange capacity per liter resin needs to be adjusted accordingly; to convert from °f to °d, multiply x 0,56; 5,5 °f
M
3
/L equals 3,1 °d M
3
/L.
(2)
When the Exchange capacity per liter resin is changed, the refill cycle time needs to be adjusted accordingly.
(1)
When the Hardness unit is changed, the Exchange capacity per liter resin needs to be adjusted accordingly; to convert from °f to °d, multiply x 0,56; 5,5 °f
M
3
/L equals 3,1 °d M
3
/L.
(2)
When the Exchange capacity per liter resin is changed, the refill cycle time needs to be adjusted accordingly.
Model
Simplex Tempo
Resin
25
50
75
100
125
150
Cycle 1: BACKWASH (min)
5
5
5
5
5
5
Cycle 2: BRINE DRAW/SLOW RINSE (min)
48
76
104
77
73
87
Cycle 3: FAST RINSE/REFILL (min)
6
6
9
12
14
17
Regen @
2:00
2:00
2:00
2:00
2:00
2:00
Model
Simplex Eco
Resin
25
50
75
100
125
150
Hardness unit
(1)
°f
°f
°f
°f
°f
°f
Exchange capacity per liter resin (°f M
3
/L)
(1) (2)
5,5
5,5
5,5
5,5
5,5
5,5
Resin (liters)
25
50
75
100
125
150
Override (days)
7
7
7
7
7
7
Cycle 1: BACKWASH (min)
5
5
5
5
5
5
Cycle 2: BRINE DRAW/SLOW RINSE (min)
48
76
104
77
73
87
Cycle 3: FAST RINSE/REFILL (min)
(2)
6
6
9
12
14
17
MTR
SNAP
SNAP
SNAP
SNAP
SNAP
SNAP
Regen
Dlyd/Immd
Dlyd/Immd
Dlyd/Immd
Dlyd/Immd
Dlyd/Immd
Dlyd/Immd
Regen @
2:00
2:00
2:00
2:00
2:00
2:00
Rsrv
Variable
Variable
Variable
Variable
Variable
Variable
Model
Duplex Eco Alternating
Resin
25
50
75
100
125
150
Hardness unit
(1)
°f
°f
°f
°f
°f
°f
Exchange capacity per liter resin (°f M
3
/L)
(1) (2)
5,5
5,5
5,5
5,5
5,5
5,5
Resin (liters)
25
50
75
100
125
150
Cycle 1: BACKWASH (min)
5
5
5
5
5
5
Cycle 2: BRINE DRAW/SLOW RINSE (min)
48
76
104
77
73
87
Cycle 3: FAST RINSE/REFILL (min)
(2)
6
6
9
12
14
17
MTR
SNAP
SNAP
SNAP
SNAP
SNAP
SNAP
Model
Duplex/Triplex Eco Parallel
Resin
25
50
75
100
125
150
Hardness unit
(1)
°f
°f
°f
°f
°f
°f
Exchange capacity per liter resin (°f M
3
/L)
(1) (2)
5,5
5,5
5,5
5,5
5,5
5,5
Resin (liters)
25
50
75
100
125
150
Override (days)
7
7
7
7
7
7
Cycle 1: BACKWASH (min)
5
5
5
5
5
5
Cycle 2: BRINE DRAW/SLOW RINSE (min)
48
76
104
77
73
87
Cycle 3: FAST RINSE/REFILL (min)
(2)
6
6
9
12
14
17
MTR
SNAP
SNAP
SNAP
SNAP
SNAP
SNAP
Regen
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Summary of Contents for ProFlow
Page 1: ...2014 Aquion Inc TM EN ProFlow Rev2014 04 Technical Manual WATER SOFTENER...
Page 18: ...HYDRAULIC FLOW DIAGRAMS Page 18 SERVICE BACKWASH BRINE DRAW SLOW RINSE FAST RINSE REFILL...
Page 19: ...Page 19...
Page 26: ...EXPLODED VIEW SIMPLEX TEMPO ECO Page 26...
Page 28: ...EXPLODED VIEW DUPLEX ECO ALTERNATING Page 28...
Page 30: ...EXPLODED VIEW DUPLEX ECO PARALLEL Page 30...
Page 32: ...EXPLODED VIEW TRIPLEX ECO PARALLEL Page 32...
Page 34: ...EXPLODED VIEW TIMER HEAD SIMPLEX Page 34...
Page 36: ...EXPLODED VIEW TIMER HEAD DUPLEX ALTERNATING Page 36...
Page 38: ...EXPLODED VIEW TIMER HEAD DUPLEX TRIPLEX PARALLEL Page 38...
Page 40: ...EXPLODED VIEW VALVE BODY Page 40...
Page 45: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 1 2 a 2 b 3 a 3 b...
Page 46: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 4 a 4 b r 5 a 5 b...
Page 47: ...2013 Aquion Inc PP ProFlow Rev2014 01 6 7 a 7 b r 8 a 8 b...
Page 48: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 9 10 r 11 r 12...
Page 49: ...2013 Aquion Inc PP ProFlow Rev2014 01 13 14 a 14 b 14 c...
Page 50: ...2013 Aquion Inc PP ProFlow Rev2014 01 15...