ELECTRONIC CONTROL PANEL
Page 13
SIMPLEX ECO
:
1.
Press the
scroll
button and hold it for 5 sec until the
display shows:
2.
Within 10 sec, press the
up
button; the display will
show:
Press the
up
or
down
button to set
the hardness
unit
.
Make sure to also adjust/convert the exchange
capacity!
3.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the
exchange capacity per litre of resin
.
4.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the volume
of resin
.
5.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the number
of days between regenerations
.
6.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the length
of the regeneration cycle
.
Press the
scroll
button again to advance to the next
regeneration cycle.
Cycle 1
Backwash
Cycle 2
Brine draw/slow rinse
Cycle 3
Fast rinse/refill
7.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the type of
water meter sensor
.
8.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to set
the
regeneration mode
:
Dlyd/Immd
: when the remaining capacity equals
the reserve capacity, a
delayed regeneration
at
the programmed time of regeneration is started;
however when the remaining capacity equals 0
before the programmed time of regeneration is
reached, an
immediate regeneration
is started.
Immediate
: when the remaining capacity equals
0, an
immediate regeneration
is started.
Delayed
: when the remaining capacity equals the
reserve capacity, a
delayed regeneration
at the
programmed time of regeneration is started.
9.
Press the
scroll
button again; the display will show
(only when the regeneration mode is set to ‘Delayed’ or
‘Dlyd/Immd’):
Press the
up
or
down
button to set
the time of
regeneration
.
10.
Press the
scroll
button again; the display will show
(only when the regeneration mode is set to ‘Dlyd’ or
‘Dlyd/Immd’):
Press the
up
or
down
button to set
the reserve
capacity
:
Variable
: the reserve capacity is calculated
automatically, based on the registered daily water
usage.
Fxd
: press the
scroll
button again and press the
up
or
down
button to set
the reserve
capacity to a fixed amount
.
11.
Press the
scroll
button again; the display will show:
Press the
up
or
down
button to save the
program into the NOVRAM® and exit the
programming level.
Cycle 1:
XX
min
System Check
Regen @
2:00
Exit
HardUnit:
°f
Resin:
XXX
liters
ExCap:
5.5
°f M3/L
Override:
7
days
MTR:
SNAP SENSOR
Regen:Dlyd/Immd
2:00
Rsrv
Variable
Summary of Contents for ProFlow
Page 1: ...2014 Aquion Inc TM EN ProFlow Rev2014 04 Technical Manual WATER SOFTENER...
Page 18: ...HYDRAULIC FLOW DIAGRAMS Page 18 SERVICE BACKWASH BRINE DRAW SLOW RINSE FAST RINSE REFILL...
Page 19: ...Page 19...
Page 26: ...EXPLODED VIEW SIMPLEX TEMPO ECO Page 26...
Page 28: ...EXPLODED VIEW DUPLEX ECO ALTERNATING Page 28...
Page 30: ...EXPLODED VIEW DUPLEX ECO PARALLEL Page 30...
Page 32: ...EXPLODED VIEW TRIPLEX ECO PARALLEL Page 32...
Page 34: ...EXPLODED VIEW TIMER HEAD SIMPLEX Page 34...
Page 36: ...EXPLODED VIEW TIMER HEAD DUPLEX ALTERNATING Page 36...
Page 38: ...EXPLODED VIEW TIMER HEAD DUPLEX TRIPLEX PARALLEL Page 38...
Page 40: ...EXPLODED VIEW VALVE BODY Page 40...
Page 45: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 1 2 a 2 b 3 a 3 b...
Page 46: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 4 a 4 b r 5 a 5 b...
Page 47: ...2013 Aquion Inc PP ProFlow Rev2014 01 6 7 a 7 b r 8 a 8 b...
Page 48: ...2013 Aquion Inc PP ProFlow Rev2014 01 r 9 10 r 11 r 12...
Page 49: ...2013 Aquion Inc PP ProFlow Rev2014 01 13 14 a 14 b 14 c...
Page 50: ...2013 Aquion Inc PP ProFlow Rev2014 01 15...