Total amount of iron to be removed between regenerations - 
 
 

÷ ppm of iron to be removed per day 

 

= NUMBER OF DAYS BETWEEN REGENERATIONS 

 

 

EXAMPLE: 

people in the household 

 

x 75 

gallons of filtered water per person 

 

= 375 

gallons of filtered per day 

 

x 4 

ppm of compensated iron - 4 is the minimum setting of compensated iron 

 

= 1,500 

PPM OF IRON TO BE REMOVED PER DAY 

 
 

6,000 

ppm capacity ÷ 2 to ensure adequate reserve capacity 

 

÷ 1,500 

ppm to be removed per day 

 

= 4 

DAYS BETWEEN REGENERATIONS 

Before Installation 

 

INSPECTION AND HANDLING

 

Inspect  the  equipment  for  any  visible  shipping  damage.  If  damaged,  notify  the  transportation  company  and  request  a  damage 
inspection. Damage to cartons should also be noted. Handle the filter unit with care. Damage can result if dropped or if set  on 
sharp, uneven projections on the floor. Do not turn the filter unit upside down.  
 

NOTE:

   If a severe loss in water pressure is observed when the filter unit is initially placed in service, the filter tank may have 

 

been laid on its side during transit. If this occurs, manually backwash the filter to “reclassify” the media. 

 

IRON (Fe) 

Iron concentrations as low as 0.3 ppm will cause staining. The iron concentration, together with the flow rate demand and the 
consumption  rate  of  the  water  determines  the  basic  size  filter  system.  The  higher  these  factors  are,  the  larger  the  required 
system. The Filter system is capable of filtering out the three main types of iron found in water supplies: Soluble iron (also known 
as “clear water” or ferrous iron), precipitated iron (also known as “red water” or ferric iron) and bacterial iron (also known as iron 
bacteria). There is no apparent upper limit of iron concentration for the filter, but special care must be taken when selecting a 
filter model if your water has a combination of high iron, very low pH and/or manganese. 

 

MANGANESE (Mn) 

The  presence  of  manganese  can  be  bothersome,  even  for  a  chemical  free  iron  filter.  As  little  as  0.05  ppm  of  manganese  can 
produce  a  brownish  or  black  stain.  If  manganese  is  present  in  your  raw  water  consult  your  Independent  Water  Tech 
representative for further recommendations. 
 

pH 

The pH of water measures its acidity or its alkalinity. Water with a pH of less than 7.0 is acidic, above 7.0 it is alkaline, and a pH of 
7.0  is  neutral. The  lower  the  pH  value  is  below  7.0  the  greater  the  acidity,  and  the  higher  the  pH  value  is  above  7.0  the  more 
alkaline. Acidic water (pH less than 7.0) is corrosive to pipes, appliances, etc. A pH of 7.0 or higher facilitates iron removal  If the 
PH of your raw water is below 7.0 please contact your Independent Water Tech representative for further recommendations. 
 

TANNINS (Humic Acid) 

Tannins (also known as humic acid) which are present in some water supplies, are the result of decaying vegetable matter. If the 
tannin concentration is above approximately 0.5 ppm, it will form a sticky coating on the media, thus rendering it incapable of 
filtering the iron. A chemical free iron filter is not recommended under this condition. If the tannin concentration is less than 0.5 
ppm, a chemical free iron filter may be installed however the life expectancy of the media bed will be shortened due to the tannin 
coating the media. 
 

 

Summary of Contents for CAN165BM-100

Page 1: ...nual Birm Filter Note 1 Read all instructions carefully before operation 2 Avoid pinched o rings during installation by applying provided with install kit NSF certified lubricant to all seals Rev 4 December 28 2011 ...

Page 2: ...ications 3 How Your System Works 3 Programming 5 Sizing Requirements 6 Before Installation 8 General Installation 10 Start Up 12 Maintenance 15 Control Valve Exploded View 16 Control Valve Parts List 17 Trouble Shooting 18 Warranty 19 ...

Page 3: ...quested by customer during a period of little or no water use The backwash cycle lasts approximately 15 minutes after which filtered water service is restored While backwashing is taking place raw water automatically bypasses the filter if required If possible avoid using water during backwashing to prevent iron laden water entering your household plumbing system This valve is controlled with simp...

Page 4: ... GALLON SETTING If the valve is not in service it will read CANATURE while the valve returns to the service position Mixed Regeneration Option This is an option that can be used on filtration units This will enable the unit to be set for gallons between regenerations with a frequency of days as an override to ensure the media bed stays in optimal working order Control Operation During A Power Fail...

Page 5: ...and press until you hear a beep to unlock the display screen Press or to select which setting to modify 2 To change setting press When the display flashes the value may be changed Press or to change the value Press to accept the value 3 Press to return to previous menu Figure 2 Program Flow Chart ...

Page 6: ...ter in order to produce the regenerate solution brine for softeners for the next regeneration cycle The water is accurately measured through the valves brine line flow control to make a precise quantity of regenerant solution 13 LOAD DEFAULT L CAPA It is not recommended to use any of these options The function of this option is to load pre set values of BACKWASH BRINE RINSE and REFILL for large me...

Page 7: ...0 PUMPING RATE ________ gals secs gpm EXAMPLE CYCLE TIME is 53 seconds DRAW DOWN is 6 gals then PUMPING RATE equals 6 gals 53 seconds x 60 6 8 gpm See chart on page two for minimum flow rates NOTE If your pumping rate is inadequate do not install your filter until problem is corrected Backwash Flow Rates The most important criteria in sizing a filter is the capacity of the pump The water must pass...

Page 8: ... ferrous iron precipitated iron also known as red water or ferric iron and bacterial iron also known as iron bacteria There is no apparent upper limit of iron concentration for the filter but special care must be taken when selecting a filter model if your water has a combination of high iron very low pH and or manganese MANGANESE Mn The presence of manganese can be bothersome even for a chemical ...

Page 9: ...ezing may cause permanent damage to this type of equipment and will void the factory warranty 6 Allow sufficient space around the unit for easy servicing THE IMPORTANCE OF YOUR PRESSURE TANK The pressure tank found on private well systems becomes an integral part of the filter system by providing necessary mixing and contact time to the Air Charged water While the iron filter will perform better o...

Page 10: ...arter full of water to protect distribution during gravel installation Slowly and carefully add the gravel support bed and the filtration media leveling each layer as it is placed into the tank Unplug the riser tube carefully position the valve over it and turn the valve into the threads in the fiberglass tank tightening securely into tank Note Ensure that the internal O ring in the valve fits sec...

Page 11: ...o the control valve as damage may result to the internal parts Check to be certain water supply pipe is connected to the control valve inlet fitting and pipe connected to control valve outlet fitting is in direction of house service 7 Perform all plumbing according to local plumbing codes 8 Use a minimum pipe or tubing size for the drain line not to exceed 10 ft 3M 9 Use a pipe or tubing for backw...

Page 12: ...1 Plug the valve into an approved power source 2 When power is supplied to the control the screen may display INITIALIZING WAIT PLEASE while it finds the service position 3 If the system has been inactive you may have to hold and press until you hear a beep to unlock the display screen Press and hold for 3 seconds to initiate a manual regeneration and advance the valve to the Backwash position Ope...

Page 13: ... and proceed with the filter installation During the time required to install the filter system the iron fouled softener resin will be chemically cleaned 4 After the filter installation is completed and final adjustments have been made turn the water back on to the softener reconnect the brine draw tube then reposition the timer on the softener to the backwash position Allow the timer to perform a...

Page 14: ... regenerations should be performed when little or no water will be used in the household New Sounds You may notice new sounds as your water filter operates The regeneration cycle lasts approximately 1 2 hour During this time you may hear water running intermittently to the drain Manual Bypass In the case of emergency you can isolate your water filter from the water supply using the bypass valve lo...

Page 15: ...en the air charger and the pressure tank are clear and free from any obstructions Notes Original settings Pumping Rate Air draw time Pressure setting Primary switch Secondary switch Split stream only Regeneration interval _________________________________________________________________________ _________________________________________________________________________ ______________________________...

Page 16: ...16 Control Valve Assembly Exploded View See parts listing on next page 17 ...

Page 17: ...nnect or 1 A 26 13000426 S crew S T2 9 13 Large W af er 2 A 27 05056038 D rai n Fi t t i ng 1 A 28 26010003 O R i ng φ 18 2 65 1 A 29 05056036 D LFC B ut t on R et ai ner 1 A 30 05056079 O R i ng φ 15 0 8 1 A 31 05056143 D LFC 2 1 A 32 05056035 B LFC B ut t on R et ai ner 1 A 33 05056191 B LFC 2 1 A 34 05056138 O R i ng φ 14 1 8 1 A 35 05056100B B LFC Fi t t i ng 1 A 36 05056106 B ri ne Li ne S cr...

Page 18: ...ar from filter tank Contact dealer for proper location of Air injector and pressure tank 5 Solenoid valve malfunction or inadequate supply system pressure flow rate Replace solenoid valve check specs for proper pressure flow rates 1 Filter bed overloaded with precipitated iron See problem above 2 Control inlet outlet valve s not fully open Open valves 3 Sand silt or mud collecting in filter bed Ch...

Page 19: ...om the date thereof Ten Year Guarantee on Mineral Tanks and Brine Tanks Canature North America Inc will provide a replacement mineral tank or brine tank to any original equipment purchaser in possession of a tank that fails within 120 months provided that the water conditioner is at all times operated in accordance with specifications and not subject to freezing Exceptions Canature North America I...

Reviews: