75
11.5 MODBUS REGISTERS
STATUS WORDS
1.
“
Config State
” –
address 0001-0002
, 32 bit unsigned. “Read only”
.
MSB
0001
LSB
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
0002
LSB
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
2.
“
System Status
” –
address 0024, 16 bit unsigned. “Read only”
.
MSB
0024
LSB
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
System Status
Bit
Name
Bit
Name
0
System Off
8
-
1
System Startup
9
-
2
System Run
10
-
3
System Cip
11
-
4
System Alarm
12
-
5
System Wait
13
-
6
System Tank Full
14
-
7
-
15
-
Bit
Name
Bit
Name
0
Feed Pump Config
16
Permeate Conductivity Tr
1
Pretreatment Config
17
Raw Water Conductivity Tr
2
Flush Valve Config
18
Cond/TDS uSm/PPM
3
Reserved
19
Imperial Units
4
Permeate Valve NC
20
Feed low pressure sensor
5
Supply Pump
21
Feed pressure sensor 4-20mA
6
Permeate Flow Tr
22
Inlet low press. sensor
7
Feed Flow Tr
23
Inlet pressure sensor 4-20mA
8
High Pressure Sw
24
RO high pressure sensor
9
Permeate Flush Config
25
RO high pressure sensor scale
0-40 bar
10
Pulse Dosing Operation
26
RO pressure sensor 4-20mA
11
Dosing Level Sw
27
Permeate pressure sensor
12
Control Valve
28
Permeate pressure sensor 4-
20mA
13
High Frequency RO
29
-
14
HQ Valve NO
30
-
15
Double Pump RO
31
-
Summary of Contents for APRO 1000 LPH
Page 1: ...aquaphor pro com TP APRO WH R02 APRO WH 1000 LPH WATER PURIFICATION SYSTEM...
Page 8: ...8 aquaphor pro com TP APRO WH R03 2 SYSTEM OVERVIEW APRO WH 1000 LPH system dimensions...
Page 9: ...9 aquaphor pro com TP APRO WH R03...
Page 13: ...13 aquaphor pro com TP APRO WH R03 3 2 ELECTRIC CIRCUIT SCHEMES...
Page 14: ...14 aquaphor pro com TP APRO WH R03...
Page 15: ...15 aquaphor pro com TP APRO WH R03...
Page 16: ...16 aquaphor pro com TP APRO WH R03...
Page 17: ...17 aquaphor pro com TP APRO WH R03...
Page 18: ...18 aquaphor pro com TP APRO WH R03...
Page 19: ...19 aquaphor pro com TP APRO WH R03...
Page 20: ...20 aquaphor pro com TP APRO WH R03...
Page 80: ...80 14 ADDITIONAL MATERIALS...
Page 81: ...81...
Page 83: ...83 REMARKS...