VCS – Viscosity Controller
4.6
Manual optimization
An optimum adaptation of the control parameters (P, I, D) is necessary in order to balance an appearing
deviation as quickly, non-oscillating and exactly as possible, according to the given operating conditions.
Generally these adjustments require a lot of professional knowledge that cannot be replaced
by this brief information.
The following information is for help purpose only:
P = proportional band Xp (%):
lower value = longer impulses, more sensitive reaction
higher value = shorter impulses, less sensitive reaction
Examples: - Oscillating temperature without distinct initial overshot: Xp too low;
- The setpoint is reached very slowly after initial exceeding: Xp too high.
I = integral action time Tn (min):
lower value = shorter impulse gaps, faster balancing
higher value = longer impulse gaps, slower balancing
Examples: - the set value is reached very slowly without overshooting: Tn too high;
- high initial overshot followed by fading oscillation: Tn too low.
D = rate time Tv (min):
increases the controller reaction in case of fast actual value or setpoint alterations
(adjust only if necessary). Higher values cause higher increase
Empirical dimensioning of Xp / Tn / Tv
Based on the actual value curves, the control loop can be re-optimized:
-
:
Actual value is only slowly approaching the set point.
Setting rule:
Increase proportional component. If this leads to an improvement, then reduce the integration time.
This repeat to one satisfactory regulator result is achieved.
-
: Actual value slowly approaches the set point with slight oscillations.
Setting rule:
Increase proportional component. If this leads to an improvement, then reduce the
-
: Actual value approaches the set point without significant overshoot.
Optimal controller behavior for processes that do not allow overshoot.
-
: Actual value is approaching the set point with a slight muted overshoot.
Optimal controller behavior for fast control and compensation of Interference components.
()
Setting rule
: The first overshoot should not be 10% of the setpoint step exceed.
-
: Actual value approaches the setpoint quickly, but oscillates far over. The Vibrations are
damped and thus just barely stable
Setting rule:
reduce proportional component. If this is an improvement leads, then increase the integration time.
This repeat to one satisfactory regulator result is achieved.
Summary of Contents for Viscosity VC312
Page 23: ...VCS Viscosity Controller 23 ...
Page 24: ...24 VCS Viscosity Controller ...
Page 25: ...VCS Viscosity Controller 25 ...
Page 26: ...26 VCS Viscosity Controller ...
Page 27: ...VCS Viscosity Controller 27 8 3 2 VC622 322 622 722 controller connection ...
Page 28: ...28 VCS Viscosity Controller ...
Page 29: ...VCS Viscosity Controller 29 ...
Page 30: ...30 VCS Viscosity Controller ...
Page 31: ...VCS Viscosity Controller 31 ...