Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
50
6
Maintenance
Ensure you have read the Safety Information in
Section 1
before undertaking maintenance.
6.1
Cleaning
✓
Clean the outside of the EMS-05. Use a
dry, clean cloth.
DO NOT
use abrasive agents or solvents to
clean the equipment.
6.2
Relays
The
Relay Maintenance
screen (
section 5.3.2
) is used to test the operation of the output relays for the Master
Panel and its ancillary devices by latching and unlatching (i.e. activating and deactivating) them.
6.3
Troubleshooting
The table below lists the most common problems and their solutions. If a problem cannot be solved then please
call support on
+44 (0)1249 715698
or visit our website at
Problem
Possible Cause
Possible Solution
System does not power on
Power
cable
is
incorrectly
connected to the Master Panel.
Check the power cable. Review
Switched fused spur
is faulty or
inactive.
Check fuses and power on the
switched fuse spur. Review
Sensor data is intermittent
or inactive
Sensors not connected properly.
Check Leader Cable and connections.
Review
Sensors not configured properly.
Review
Leak detected but no leak
present
Sensor cable is touching something
conductive.
Check Leader Cable and connections.
Review
Sensor cable is over 100 metres in
length.
Sensor cable had debris on it.
Clean sensor cable.
Ethernet network
connection is intermittent
or inactive
Network has not been configured
properly (e.g. DHCP not enabled).
Ensure DHCP and Modbus are not both
enabled. Review
Serial Link network
connection is intermittent
or inactive
Network has not been configured
properly (e.g. Modbus not enabled).
Ensure DHCP and Modbus are not both
enabled. Review
Email Alerts are
intermittent or inactive
Email Alerts have not been
configured properly.
Review
Table 15:
Troubleshooting