Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
16
B.
Sensor Cable (SCY) using LC10/LCB100 and Start of Line
Figure 8:
Sensor Cable using LC10/LCB100 and Start of Line
Connect the Sensor Cable using LC10/LCB100 and Start of Line as follows:
1.
Ensure that the unit is powered OFF.
Connect the
leader cable
into the
sensor
input terminals
on the
interface board
. Do
not connect the green or white cores
(
2.
When connecting the leader cable to its
respective sensor input terminals, ensure
that the factory-issued
terminating resistor
is removed. Retain all resistors for future
fault finding/testing.
3.
Cable the opposite end of the
leader cable
in to the
Start of Line
4.
Plug the
sensor cable
into the connection
on the
SOL
.
5.
Once all sensor cables are connected, plug
the
End of Line (EOL) terminator
into the
end of the last run of the
sensor cable.
LOOP TERMINAL
block not used
Green and white
cores not used
Belden 9534 Cable to
EMS Zone Input
Secure cable under clamp
strap
SENSE TERMINAL
Red Core: +/1
Black Core: -/2