10K manual
Issue 1.0, 31st July 2019
Page 29
Register Name
Description
Units
Range
38001
Leak Distance
Leak distance in meters -
float point - displays with
a tenths place decimal
value. This register must
be viewed and displayed
as float inverse.
Meters
0.0-9999.9
38003
Cable Length
Cable length in meters -
float point - displays with
a tenths place decimal
value. This register must
be viewed and displayed
as float inverse.
Meters
0.0-9999.9
Table 8 Status Flags (Register 30001)
Bit
Description
00
1 = Leak detected
01
1 = Cable break detected
02
1 = Contamination detected
03
1 = Summary alarm
04-15
Spare
RTU FRAMING
The example below shows a typical Query/Response from an Aqualeak 10K.
Table 9 Response sample
Slave
Address
Function
Code
Count
Bytes of
Data
Register
Data
Register
Data
Register
Data
CRC
16
CRC
126
Msb
Lsb
Msb
Lsb
Msb
Lsb
“Lsb”
“Msb”
02
04
06
00
00
00
00
00
01
B5
A3
Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with
a CRC16 checksum.
Register Values:
40001 = 0000 (hex)
40002 = 0000 (hex)
40003 = 0001 (hex)