INSTALLATION AND CONFIGURATION
PREPARATION FOR INSTALLATION
Check that all items supplied with the Aqualeak 10K, and all optional items required for your
installation, are present and undamaged. Refer to the list on Pages 10 and 11. If any items
are missing or damaged, report it before installing the equipment.
INSTALLING THE AQUALEAK 10K
Install the Aqualeak 10K on a wall, in a suitable location, as follows:
1.
Remove and retain the four flat head screws that secure the front panel of the
Aqualeak 10K. Remove the front panel.
2.
Refer to Figure 4. Using the
mounting points provided on the 10K’s back box, s
ecurely
mount the 10K’s back box in a suitable location, making cable entries as required.
Bring cables through into the back box before starting to make final connections.
ESTABLISH PHYSICAL CONNECTIONS
Connect the Aqualeak 10K as follows:
WARNING
–
ELECTRIC SHOCK
The Aqualeak 10K operates using mains voltage that is dangerous to life. Before
work commences, make sure that the mains power is isolated by a competent
person and a Lock Out and Tag-Out procedure has been followed. Prove the mains
supply is de-energised with a suitable multi-meter which has been checked with a proving
unit.
Death, personal injury and/or damage to persons and/or property may result if this is not
observed.
1.
If not already done, a competent person must install a 230 VAC fused spur near to the
Aqualeak 10K. The fused spur must be clearly marked as the disconnecting device for
the Aqualeak 10K.
CAUTION
–
EQUIPMENT DAMAGE
When connecting the mains power to the Aqualeak 10K make sure that the correct
polarity is observed. Reversing the polarity of the live and neutral connections will
result in damage to the 10K unit.
2.
Connect the Aqualeak 10K unit to the fused spur as shown in Figure 4. Connections
must be made to the Neutral/Earth/Live terminal blocks as shown in Figure 4.
NOTE
When delivered, the Aqualeak 10K already has the internal power connections
between the terminal blocks and the PSU, between the terminal blocks and the
bus bars, and between PSU and 10K Controller.