26
Setting the Aqualogic 2000™ Status Display Board:
Adjust the dipswitches, per system requirements.
1)
SW-5 Display Primary Time/Cycle
There are two elapsed clock memories in the system. One is the elapsed
time that can be reset with SW-2 and the total accumulated time. The
SW-5 switch allows the user to display the total accumulated operational
hours and cycles on the unit. Reinitializing the system erases the total
accumulated operational and cycle memory.
2)
SW-3 Set UV Sensor 0 & 100%
The SW-3 sets the UV intensity 100% set point. When pressed, the
relative intensity is set into the memory; this is the 100% set point. When
80% of the value is reached, the low UV intensity indicator is activated.
3)
SW-2 Reset Time/Cycle Counter
The SW-2 switch resets the total elapsed time and cycle counter to zero.
This switch is used when the lamps are replaced.
4)
SW-8 Status Display Board Lamp Assignments
Model
#
Lamp
Quantity
Switch
Position 1
Switch
Position 2
Switch
Position 3
Switch
Position 4
HX12 12 OPEN CLOSED
CLOSED OPEN
HX10 10 CLOSED OPEN CLOSED OPEN
HX8 8 OPEN OPEN CLOSED
OPEN
HX6 6 CLOSED
CLOSED OPEN OPEN
HX05 5 CLOSED
CLOSED OPEN OPEN
HX4 4 OPEN CLOSED OPEN OPEN
NOTE:
Down is “OPEN”, Up is “CLOSED”.
1
2
3
4
5
6
7
8
9
10