AQC Dust Collecting Systems
Electrical connection for DCT-500
sequencer
The
Maxiflo-VC
unit is equipped with 115
VAC solenoids which activate the cleaning
valves. Those solenoids are integrated in a
NEMA 4/12 box behind the filter cabinet and
above the air tanks. Connections for those
solenoids are factory wired. The DCT-500
sequencer activates the solenoids in a cascading
sequence operating the cleaning valves.
Drawing # 5 shows a typical connection for a
DCT-500 sequencer with starter. The electronic
board is activated upon fan start up using an
auxiliary contact. The electronic board is fitted
in a NEMA 4/12 box.
To activate the pulse cleaning system when the
fan is OFF, install a selector or timer with
constant feed on the inlet connector of the
electronic board.
Refer to page 2 of this document to program the
sequencer.
DCT-500 board specifications
Number of connectors: 4, 6, & 10
Power: 102-132 VAC 50-60 Hz.
Consumption : 2.5 W.
Power to solenoids: 3A max. per connector
Fuses: Type 3 AG, 3 A @ 250 VAC.
Temperature range : -40 to 140°F (-40 to 60°C)
Shutter time : 50 msec to 500 msec.
Shutter time accuracy : ±10 msec.
Shutter time stability : ±1 msec.
Lapse sequence : 1 second to 180 seconds.
Lapse sequence precision: ±5% settings.
Weight: 9 oz (255 g).
Approval agency: CE (pending).