M982282AP-03-13A
REG-6S-100
/
REG-12S-100
- 7 -
3.1
Display screen
REG-6S-100
and
REG-12S-100
devices are equipped with a 3 digits x 7 segments LCD screen. The
screen has also a set of icons, which provide information about the regulator status. The main indications
are:
cosφ value, reactive power sign (
for lagging or inductive PF and
for leading or capacitive
PF), connected stages and measurement of different parameters (see section 3.2)
Icons
Screen and LED
Icons Indications
: Lagging or inductive
power indication
: Leading or capacitive
power indication
The
LED (red) is ON
in normal working conditions
The
LED shows
that the reading of current or
max. current has to be
multiplied by 10
In normal working conditions, RUN
LED (red) is ON and
cursor
points to the parameter being
displayed (Left column list)
In SET-UP mode, the RUN LED is
OFF, the cursor is blinking and
pointing to the parameter being
configured (Right column list).
Symbols indicating the stages
which are connected (only in RUN
mode)
3.2
Measured parameters
When the instrument is in normal RUN mode, the following parameters can be displayed: cos
, mains
current, THD of both mains current and mains voltage. The instrument can also display the maximum
values of mains current and voltage since the last parameters clear. The parameter being displayed can
be selected with the navigation keys and is indicated by the cursor.
3.3
Errors and ERROR messages
In case that the regulator detects a possible error, the front screen shows an error code. The possible
error codes are listed and explained in table 3-1.
Table 3-1: Possible errors and messages displayed on the screen
ERROR
message
Description
Load current below the threshold current, or current transformer (CT) not
connected. The threshold is 0,1 A at the secondary side of CT
Overcompensation. The regulator detects that some stages should be
disconnected but all the stages are already disconnected.
Under-compensation. The regulator detects that some stages should be
connected and all the stages are already connected.
Overcurrent. The measured current exceeds the rated current by a + 20%.
(Rated current is considered to be the CT primary rated current)
Overvoltage. The measured voltage exceeds the rated voltage by a +15%.
3.4
Alarm relay
In case that the number of stages configured in a
REG-6S-100
or
REG-12S-100
, is less than 6 or 12
respectively, the relay number 6 or 12 is automatically configured as alarm relay. The relay remains
connected in absence of alarm (positive safety) and disconnects in case that one or more of the errors
listed in section 3.2 occur. Notice that the absence of supply voltage will always be detected as an alarm
condition. The alarm relay has a delay of 10 s in case of Over-compensation and Under-compensation,
but the operation is instantaneous (delay < 1 s) in case of Over-voltage and Over-current.