7.2
REG-6S-100 and REG-12S-100 behaviour in ALARM mode
In case that the
REG-6S-100
and
REG-12S-100
detects an error during normal operation (see
paragraph 3.2) the screen displays an error code and the behaviour of the device is as described in table
7-.1.
Table 7-1:
REG-6S-100 and REG-12S-100
behaviour under ALARM conditions
ERROR
message
Description
Possible cause and REG-6S-100 and REG-12S-100
behaviour
Measured current below
threshold (
0,05A measured
at the secondary side of CT)
PosSible causes:
TC low load or not connected.
The device displays the RUN LED and display all zeros
flashing and not connecting any relay.
Over-compensation
.
The
controller
demands
for
stages disconnection and
they are all disconnected.
Possible causes:
C/K not properly adjusted
None of the realys will connect.
Sub-compensation
.
The
controller
demands
for
stages connection and they
are all connected.
Possible causes:
C/K not properly adjusted
All the relays will remain connected, except the alarm relay
if exists (see paragraph 3.3)
Overcurent.
The measured
current is 20% above the
rated current (primary of CT)
Possible causes:
C/K not properly adjusted
Alarm relay, if exists, disconnects (see paragraph 3.3)
Although the regulation may be wrong, the device tries to
regulate the PF normally.
Overvoltage.
The
measured voltage is 15%
above rated voltage.
Possible causes:
Connection to a wrong supply voltage.
Alarm relay, if exists, disconnects (see paragraph 3.3)
Although the regulation may be wrong, the device tries to
regulate the PF normally.
8
MAINTENANCE
REG-6S-100 and REG-12S-100
do not require a special maintenance program. In case that some
adjustments or maintenance might be necessary it must be performed by dully qualified staff and
respecting the required safety procedures.
If any malfunction of the PF compensation equipment or associated protections is detected, the
equipment should be disconnected from mains. Before performing any maintenance repair or update
operation on the computer or associated PF compensation equipment, be sure to disconnect the main
switch and after disconnecting the switch, wait at least 5 minutes to ensure that the capacitors are totally
discharged.
9
TECHNICAL SERVICE
In case of any doubt on the behaviour of the device or in case of malfunction which cannot be solved by
the maintenance staff, contact APS technical service:
Advanced Power Systems, APor technical support
Phone. - 001 514 4478282
(Canada)
For middle East services
Phone. - 00971 4 3263950
(Dubai)
www.apsme.com
e-mail - [email protected]