5.2 AC input terminal connection
After the DC terminal is connected, do not close the DC switch first. Connect the
AC terminal to the AC terminal of the inverter; the AC terminal is equipped with
three-phase AC terminals that can be conveniently connected. Flexible cords are
recommended for ease of installation. The specifications are as shown in Table
5.2.
Cable dia
Cable CSA
Cable outer dia
AWG
Specification
2.5mm
10mm
2
15-18mm
8
Model
APSG-3-(5.5-12K)-
IN
APSG-3-15K-IN
APSG-3-20K-IN
APSG-3-25K-IN
Breaker
22A/400V
30A/400V
36A/400V
50A/400V
Max cable length
Outside cable(3+PE)20m
Table5.2 Cable information
1. Matching socket 2.Sleeve 3.Sealing sleeve
Pic5.7 AC connector structure
The AC output connector is divided into three parts: matching socket, sleeve and
sealing sleeve, as shown in Picture 5.7, the steps are as follows:
Step 1: Remove the cable sealing ring and sleeve in sequence from the AC
connector.