background image

20

 -

English

SWING APRICODE 230

CONTROL UNIT

SYSTEM START-UP

3. 

When the power supply to the unit is switched ON, 

the following information is shown on the display: the 

FIRMWARE release NUMBER

 and the name of the system. 

When this information is no longer displayed the unit can 

be operated.

When the power supply is switched ON to the unit for the 

fi

 rst  time, 

Lrn

 

fl

 ashes on the display: preliminary checks 

and the self-teach procedure must be performed.

P

3.1 

reliminary checks: inputs - movement direction 

- operator parameters

Make the following checks and settings when 

Lrn

 

fl

 ashes 

on the display:

INPUT CHECKS

During the 

Lrn

 phase, the fourth display on the card shows 

the status of the inputs (

fi g.2

).

MOVEMENT DIRECTION CHECK (OPEN / CLOSE) 

During the 

Lrn

 phase and with the gate is closed, move the 

wings using the special button (

fi g.3)

 and check that:

- The FIRST time the YELLOW or BLUE button is pressed   the 

relevant wing is OPENED.

If this does not occur then you must adjust the parameter 

d1

 and/or 

d2

 

(press the RED button to access programming)

.

OPERATOR PARAMETERS CHECK

During the 

Lrn

  phase, press the 

RED

 button to access 

programming (

fi g.4

) and if necessary modify the 

Mod

 and 

rEL

, parameters in accordance with the type of operator 

installed (

see the 

Programming section)

.

Self-teach movements

3.2 

The unit learns the point at which SLOWING STARTS and the 

stroke of the movement (STOPPING point).

During the 

Lrn

 phase, press the START controls in sequence 

for the self-teach procedure:

START   OPENING starts;

START   SLOWING starts;

START   STOP;

START   CLOSING starts;

START   SLOWING starts;

START   STOP.

If there are two wings then the sequence is wing 1 then 
wing 2  OPENING and wing 2 then wing 1 CLOSING (fi g. 6).

Warning

!

External signals are ignored during the self-teach procedure 
except for the photocell during closing and STOP signals. If 
these signals are triggered the self-teach procedure is stopped 
and must be repeated.

IMPORTANT!

 The START command to self-teach the STOPPING point 

during opening and closing must be given when the wing 

reaches the mechanical stop. The additional thrust at the end 

of the movement is managed by the parameter (

ta

-

t1

).

 The self-teach procedure for slowing differs in accordance 

with the features of the operator installed:

 Hydraulic operators without 

hydraulic slowing and the

 

Electro-

mechanical

 operators use 

electronic slowing

. The self-teach 

procedure identi

fi

 es the start points, therefore the START 

command must be given when the wing reaches the point 

at which you require slowing to start (WARNING: 

rEL

=

1

).

Special operation during 

fi g. 3 -  

lrn

 status:

to move the wings press and hold:

wing1

• 

   

YELLOW button

wing2

• 

   

BLUE button

Each time the button is released and then pressed again, 
the movement of the relevant wing is reversed.

      

 

 

MOVES

 

WING

 1    

   

 

 

MOVES

 

WING

 

2

BLUE

 

YELLOW

 

Access to programming during 

fi g. 4 -  

lrn

Access to parameters during 

Lrn

:

 

 

 

LO

.

0

RED

 

L r N _

_

-

display 4 during 

Lrn

: INPUTS

(segment ON = contact closed)

L r N _

_

-

__

2

4

5

6

7

2 = CLOSING PHOTOCELL

4 = PEDESTRIAN START

5 = SAFETY DEVICE during OPENING

6 = START

7 = STOP

During standby, segments 2, 7 and 5 fl ash if the relevant 
connections or jumpers are correct.

Testing of inputs during 

fi g. 2 -  

lrn

Start of movements during SELF-TEACH

fi g. 5 -  

Start the self-teach movements:

L r N _

_

-

 

START

  

(

Ö

FA 1

 

)

 

fi g.7

  

note: while the display shows 

FA1

 the gate can be stopped 

and the 

Lrn

 phase re-accessed. Simply press the YELLOW 

button or the STOP control if connected.

display

during 

LRn

Summary of Contents for SWING 230 APRICODE

Page 1: ...una marca registrada de Aprimatic S p A ZWECK DES HANDBUCHS Dieses Handbuch wurde vom Hersteller verfasst und ist ein erg nzender Bestandteil des Produkts Es enth lt alle n tigen Informationen f r di...

Page 2: ...liary safety S curit auxiliaire Zus tzliche Sicher Seguridad auxiliar CLPh Fotocellula in chiusura Closing photocell Photocellule en fermeture Lichtschranke beim Schlie en Fotoc lula en cierre CND Con...

Page 3: ...ne di rete 6 3 Avvio del sistema 8 3 1 Verifiche preliminari ingressi senso di marcia parametri attuatore 8 3 2 Manovre di apprendimento 8 3 3 Funzionamento di DEFAULT 9 3 4 Attivazione Autoapprendime...

Page 4: ...emergenza e consegnare le istruzioni d uso all utilizzatore dell impianto Per eventuali riparazioni o sostituzioni dovranno essere utilizzati esclusivamente ricambi originali Non si riconosce la garan...

Page 5: ...novra successiva al ripristino e allo START avverr in modalit di SICUREZZA cio a VELOCIT RIDOTTA con il lampeggiante acceso fisso e completando il movimento di un anta per volta Al fine di consentire...

Page 6: ...ndo le norme vigenti Dimensionare opportunamente la sezione del cavo in base alla lunghezza della linea IMPORTANTE Installare sempre a monte della linea un interruttore generale che garantisca una sco...

Page 7: ...er confermare l opzione visualizzata ATTENZIONE i contatti N C devono essere ponticellati verso massa morsetto 10 12 quando non vengono utilizzati In caso contrario l automazione NON PUO funzionare co...

Page 8: ...Attenzione Durante l autoapprendimento vengono ignorati i segnali esterni a esclusione della fotocellula durante la chiusura e dei segnali di STOP Se questi intervengono interrompono l autoapprendime...

Page 9: ...CA AUTOMATICA logica di default Lo 0 Il ciclo completo di funzionamento il seguente START a cancello chiuso il cancello apre fino a completamento manovra resta aperto per il TEMPO DI PAUSA settato all...

Page 10: ...a prima conferma con il ROSSO1 Per CANCELLARE un solo telecomando parametro rn scorrere fino all indirizzo del telecomando da cancellare e dare la prima conferma con il ROSSO1 Per migrare tutti i tele...

Page 11: ...in chiusura riapre blocca1 riapre blocca2 in apertura blocca1 blocca1 inverte e blocca blocca2 bloccata da STOP chiude 4 PASSO PASSO INGRESSO STATO AUTOMAZIONE START STOP SICUREZZA IN CHIUSURA SICURE...

Page 12: ...ne programmata Se non si utilizza il lampeggiatore occorre disabilitare il prelampeggio lam settando il tempo a 0 sec Lampada spia per la segnalazione remota dello stato dell automazione luce spenta a...

Page 13: ...l termine della chiusura i motori vengono azionati in senso inverso per il tempo settato per scaricare i cinematismi della meccanica A9 Velocit in accostamento 30 1 30 2 40 VELOCIT DI MANOVRA rat Sett...

Page 14: ...orda che le batterie in quanto materiale di consumo non sono coperte da garanzia Si raccomanda di non disperdere la batteria nell ambiente ma di utilizzare gli appositi contenitori previsti presso i p...

Page 15: ...ns 18 2 4 Connecting up to the mains power supply 18 3 System start up 20 3 1 Preliminary checks inputs movement direction operator parameters 20 3 2 Self teach movements 20 3 3 DEFAULT functioning 21...

Page 16: ...orking area unattended We recommend strict observation of the national regulations for safety in work sites in Italy Legislative Decree 528 99 combined with Legislative Decree 494 96 Implementation of...

Page 17: ...t gate movement after RESET and START occurs in SAFE mode i e at REDUCED SPEED with the flashing light permanently ON and with movement taking place one wing at a time This mode is also set for the ne...

Page 18: ...ctrical regulations Choose the section of the cable to match the length of the line IMPORTANT Always install upstream of the line a mains switchwhichguaranteesamultipolecut offwithminimum contact open...

Page 19: ...1 CN1 CN2 J1 DS1 DS2 DS3 DS4 FS1 FS2 JRX FS3 FS4 FS5 J12 CN3 J16 L N J11 1 2 FS6 FS7 J13 J14 PH N GND M2 M1 encoder 1 encoder 2 12VAC 15W max J16 photocell transmitting when negative standard photocel...

Page 20: ...ence is wing 1 then wing 2 OPENING and wing 2 then wing 1 CLOSING fig 6 Warning External signals are ignored during the self teach procedure except for the photocell during closing and STOP signals If...

Page 21: ...modify the functioning parameters AUTOMATIC MODE default logic Lo 0 The complete operating cycle is a follows START with the gate closed the gate opens completely remains open for the PAUSE TIME set c...

Page 22: ...e RED button1 ToDELETEanindividualremotecontrol parameterrn scroll to the address of the remote control you wish to delete and confirm using the RED button1 To export all the remote controls saved you...

Page 23: ...e opens locks1 re opens locks2 opening locks1 locks1 reverses and locks locks2 locked using STOP closes 4 STEP BY STEP INPUT AUTOMATION STATE START STOP CLOSING SAFETY AUXILIARY SAFETY SAFETY EDGE PHO...

Page 24: ...itions flashing every 0 5 sec routine maintenance required If the flashing light is not used then the pre flashing function must be disabled lam by setting it to 0 seconds Warning light this is a remo...

Page 25: ...hemotorsareoperatedinreversedirectionforthe timesettodischargethemechanismswhenmovementiscomplete A9 Approach speed 30 1 30 2 40 OF MOVEMENT SPEED rat Factory setting Do NOT modify 0 2 DO NOT MODIFY L...

Page 26: ...ou start any maintenance operations disconnect the automation from the mains power supply using the system electrical differential switch Batteries are consumables and as such are not covered by the g...

Page 27: ...ctriques 30 2 4 Raccordement la tension de secteur 30 3 D marrage du syst me 32 3 1 Contr les pr liminaires entr es sens de marche param tres op rateur 32 3 2 Man uvres d apprentissage 32 3 3 Fonction...

Page 28: ...specter les normes nationales en vigueur pour la s curit des chantiers en Italie D cret l gislatif 528 99 coordonn avec le d cret l gislatif 494 96 Application de la directive 92 57 CEE concernant les...

Page 29: ...vre qui suit le r tablissement et la MARCHE a lieu en mode S CURIT c est dire VITESSE R DUITE avec le clignotant allum fixe et en effectuant le mouvement d un vantail la fois Afin de r aligner le port...

Page 30: ...n de c ble adapt e la longueur de la ligne IMPORTANT Toujourspr voiruninterrupteurg n ralenamont delalignepourgarantiruned connexionomnipolaireavecune ouvertureminimumdescontactsde3mm relier undisjonc...

Page 31: ...acts N F doivent tre pont s c t masse borne 10 12 quand ils ne sont pas utilis s Autrement l automatisme NE PEUT PAS fonctionner J16 au n gatif photocellule mettrice photocellules standard ou la borne...

Page 32: ...o apprentissage les signaux ext rieurs ne sont pas pris en consid ration except la cellule photo lectrique pendant la fermeture et les signaux d ARR T Lorsque ces derniers se d clenchent ils provoquen...

Page 33: ...p Programmation MODE AUTOMATIQUE mode par d faut Lo 0 Le cycle de fonctionnement complet est le suivant MARCHE avec le portail ferm le portail s ouvre jusqu ce que la man uvre soit termin e il reste o...

Page 34: ...on avec le bouton ROUGE1 Pour EFFACER une seule t l commande param tre rn faire d filer jusqu l adresse de la t l commande effacer et confirmer avec le bouton ROUGE1 Pour la migration de toutes les t...

Page 35: ...loque2 en phase d ouverture bloque1 bloque1 inverse et bloque bloque2 bloqu e parARR T ferme 4 PAS PAS ENTR E TAT AUTOMATISME MARCHE ARR T S CURIT EN PHASE DE FERMETURE S CURIT AUXILIAIRE BORD SENSIBL...

Page 36: ...ode s curit intermittence de 0 5 s entretien programm exig En cas d inutilisation du clignotant d sactiver le pr clignotement lam en r glant le temps sur 0 s Voyant pour signaler distance l tat de l a...

Page 37: ...ensinversependant letempss lectionn pourpermettredesoulagerlachargesurlesvantaux A9 Vitesse d approche 30 1 30 2 40 VITESSE DE MAN UVRE rat R glage d usine NE pas modifier 0 2 NE PAS MODIFIER LUM Lumi...

Page 38: ...es batteries tant des consommables elles ne sont pas couvertes par la garantie Il est recommand de ne pas jeter la batterie dans la nature mais d utiliser les r cipients pr vus cet effet dans les poin...

Page 39: ...he Anschl sse 42 2 4 Anschluss an die Netzspannung 42 3 Start des Systems 44 3 1 Vorbereitende Kontrollen Eing nge Laufrichtung Parameter des Antriebs 44 3 2 Selbstlernvorgang 44 3 3 Standardbetrieb 4...

Page 40: ...endung von Komponenten einer anderen Marke verf llt der Garantieanspruch Der Hersteller des Antriebs lehnt jede Haftung ab wenn Komponenten installiert werden die f r die Zwecke der Sicherheit und des...

Page 41: ...rfolgt im SICHERHEITSBETRIEB d h mit REDUZIERTER GESCHWINDIGKEIT DieBlinkleuchteleuchtetmitDauerlicht und es wird die Bewegung jeweils eines Torfl gels zu Ende gef hrt Damit das Tor wieder in der beka...

Page 42: ...ieren der eine allpolige Abschaltung mit 3 mm Mindest ffnung der Kontakte garantiert an einen 6 A FI Schalter mit 30 mAAusl sestrom anschlie en J1 Anschluss f r serielle Schnittstelle RS232 Urmet Schn...

Page 43: ...S3 FS4 FS5 J12 CN3 J16 L N J11 1 2 FS6 FS7 J13 J14 PH N GND M2 M1 encoder 1 encoder 2 12VAC 15W max J16 zum Minuspol Lichtschrankensender Standardlichtschranken oder zur KlemmeTST Lichtsch Typ REFLEX...

Page 44: ...SCHLIESSUNG zuerst f r Fl gel 2 dann f r Fl gel 1 durchgef hrt Abb 6 Achtung ExterneSignalew hrenddesSelbstlernzykluswerdenignoriert ausgenommen davon sind die Lichtschranke beim Schlie en und die STO...

Page 45: ...den der vollst ndige Betriebszyklus START mit geschlossenem Tor das Tor ffnet sich bis zum Ende des Vorgangs bleibt f r die Dauer der eingestellten PAUSENZEIT ge ffnet und schlie t sich nach Ablauf de...

Page 46: ...se des zu l schenden Handsenders scrollen und f r die erste Best tigung die ROTE Taste1 dr cken Zum Migrieren aller gespeicherten Handsender ist das herausnehmbare Speichermodul siehe Katalog erforder...

Page 47: ...perre2 beim ffnen Sperre1 Sperre1 Richtung umkehren und sperren Sperre2 gesperrt mit STOP schlie en 4 SCHRITTBETRIEB EINGANG STATUS DER AUTOMATIK START STOPP SICHERHEIT BEIM SCHLIESSEN ZUS TZLICHE SIC...

Page 48: ...Dauerlicht Sicherheitsbetrieb Blinkfrequenz 0 5 s Planm ige Wartung f llig Wenn die Blinkleuchte nicht verwendet wird muss das Vorblinken lam durch Einstellen der Zeit auf 0 Sek ausgeschaltet werden...

Page 49: ...6 150 7 200 8 300 9 400 MS AmEndederSchlie bewegungwerdendieMotorenf rdieeingestellte ZeitinumgekehrteRichtunggesteuert umdieMechanikzuentlasten A9 Ann herungsgeschwindigkeit 30 1 30 2 40 BET TIGUNGSG...

Page 50: ...als Verbrauchsmaterial nicht unter die Garantie fallen Entsorgen Sie die verbrauchte Batterie grunds tzlich nur in den hierf r vorgesehenen Beh ltern in den Verkaufsstellen der Batterien HINWEISE F R...

Page 51: ...4 Conexi n de la tensi n de red 54 3 Puesta en marcha del sistema 56 3 1 Controles previos entradas direcci n de marcha par metros actuador 56 3 2 Maniobras de aprendizaje 56 3 3 Funcionamiento por D...

Page 52: ...zonadetrabajo Se aconseja respetar rigurosamente las normas nacionales v lidas para la seguridad en las obras en Italia D Lgs 528 99 coordinado con D Lgs 494 96 Transposici n de la Directiva 92 57 CEE...

Page 53: ...a maniobra sucesiva al restablecimiento y al START se realizar en modo de SEGURIDAD es decir a VELOCIDAD REDUCIDA con la luz destellante encendida con luz fija y completando el movimiento de las hojas...

Page 54: ...l nea IMPORTANTE Instalar siempre l nea arriba de la l nea un interruptor general que garantice la desconexi n omnipolar con una apertura m nima de los contactos de 3 mm conectar a un interruptor magn...

Page 55: ...FASE TIERRA NEUTRO LEYENDA M1 motor 1 a hoja en apertura M2 motor 2 a hoja en apertura ROJO VERDE ROJO AZUL NEGRO AMARILLO AMARILLO SECUNDARIO 9 0 9 VAC PRIMARIO 230 VAC SECUNDARIO 12 VAC Electrocerra...

Page 56: ...Durante el autoaprendizaje se ignoran las se ales externas excepto las de la fotoc lula durante el cierre y las se ales de STOP Si estas se ales intervienen interrumpen el autoaprendizaje por lo que e...

Page 57: ...ciclo completo de funcionamiento es el siguiente START con cancela cerrada la cancela abre hasta que se complete la maniobra permanece abierta durante el TIEMPO DE PAUSA configurado cuando finaliza el...

Page 58: ...primera confirmaci n con la tecla ROJA1 Para BORRAR s lo un mando a distancia par metro rn situarse en la direcci n del mando a distancia que se quiere borrar y dar la primera confirmaci n con la tecl...

Page 59: ...vuelve a abrir bloquea2 en apertura bloquea1 bloquea1 invierte y bloquea bloquea2 bloqueada por STOP cierra 4 PASO PASO ENTRADA ESTADO AUTOMATIZACI N START STOP SEGURIDAD EN CIERRE SEGURIDAD AUXILIAR...

Page 60: ...cia de 0 5 seg petici n de mantenimiento programado Si no se utiliza la luz destellante hay que inhabilitar el predestello lam configurando el tiempo en 0 seg L mpara piloto para la indicaci n remota...

Page 61: ...del cierre los motores se accionan en sentido inverso durante el tiempo configurado para descargar los cinematismos de la mec nica A9 Velocidad en acercamiento 30 1 30 2 40 VELOCIDAD DE MANIOBRA rat...

Page 62: ...el ctrica Se recuerda que la garant a no cubre las bater as ya que son materiales de consumo Se recomienda no abandonar la bater a en el ambiente sino utilizar los dep sitos adecuados situados en los...

Page 63: ...63 SWING 230 APRICODE...

Page 64: ...SWING 230 APRICODE Aprimatic S p A via Leonardo da Vinci 414 40059 Villa Fontana di Medicina Bologna Italia Tel 39 051 6960711 fax 39 051 6960722 info aprimatic com www aprimatic com...

Reviews: