COMMAND
DESCRIPTION
VALUE
Communication Control Commands
CR
Command Response Control
Silent / Quiet / Normal
C1
Change of State (COS) – HVAC relays
ON/OFF
C2
COS – Temperature
ON/OFF
C3
COS – Remote Temperature
ON/OFF
C5
COS – Set Points
ON/OFF
C6
COS – Network Override
ON/OFF
C7
COS – Mode
ON/OFF
C8
COS – Fan
ON/OFF
HOLD
User Hold Status
ON / OFF
NAME
Location Name
<String>
ID
Report Model No. and software rev.
Read Only
Thermostat Sensing Commands
SCALE
Command Temperature Scale
F / C (Fahrenheit/Celsius)
TEMP, T
Report Thermostat Room Temperature
Read Only
HUM
Report Thermostat Room Humidity
Read Only
(requires humidity control sensor)
RSM
Identify all external sensors connected
Read Only
to a thermostat’s local communication network
RxSy
Report value of any sensor on thermostat’s
Read Only
(x = 1-4; y = 1,2)
local communication network
OT
Report Thermostat Remote “Outdoor” Temperature
Read Only
R
Report Thermostat Remote “Outdoor” Temperature
Read Only
OH
Report Thermostat Remote Humidity
Read Only
Thermostat HVAC Operational Commands
SH
Heat Mode Set Point
Two or three digit integer: 40 – 88 for °F; 4 – 31 for °C
SH++
Increment heat set point
Integer value which when added to the current heat
set point does not fall outside the SH limits
SH--
Decrement heat set point
Integer value which when deducted from the current
heat set point does not fall outside the SH limits
SC
Cool Mode Set Point
Two or three digit integer: 42 – 90 for °F; 6 – 33 for °C
SC++
Increment cool setpoint
Integer value which when added to the current cool
set point does not fall outside the SC limits
SC--
Decrement cool setpoint
Integer value which when deducted from the current
cool set point does not fall outside the SC limits
S
Current Mode Set Point
Two or three digit integer (see next two commands)
SP++
Increment current mode set point
Integer value which when added to the current mode
set point does not fall outside the SH and SC limits
SP--
Decrement active setpoint
Integer value which when deducted from the current mode
set point does not fall outside the SH and SC limits
MODE, M
Thermostat Mode of Operation
A /C /H /E/OFF (Auto/Cool/Heat /EMHT/Off)Humid/Dehum
when operating as a humidity controller
FAN, F
Fan Switch Setting
A /ON (Auto /On)
HVAC, H
Report HVAC Relay States
Read Only
Auxiliary Information Commands
EQUIPCONFIG
Reports the setting of the thermostat
Read Only
configuration dip switches
BLTON
Turns on backlighting for 10 seconds.
No Value Required for this Command
20
MODEL 8870 BASIC COMMAND SET