MODEl 8910 HOME COMfORT CONTROl

 

OR THIRD-PARTy CONTROl

WIRING & DIP SWITCH CONfIGURATION

When used as an external control, the Model 8910 Home Comfort Control

 or other third-party control acts like a dehumidistat and will turn 

the dehumidifier on and off when the relative humidity goes above or below the setting . 

The Model 8910 Home Comfort Control

 or other 

Third-Party Control must be installed in the space that is being served by the dehumidifier.

 One example of this would be to install the 

Model 8910 Home Comfort Control

 in the home’s living space and wire it to the dehumidifier which is located in the basement and is ducted 

to the HVAC system . The Model 8910 Home Comfort Control

 or other third-party control will override the dehumidifier control sensors and 

on-board control knob setting . Refer to the Model 8910 Home Comfort Control

 or other third-party control Installation Instructions for location, 

mounting, and operating instructions . The dehumidifier control knob can only be used to initiate Test Mode when a Model 8910 Home Comfort 
Control

 or other third-party control is connected .

fIGURE 32 – Third-Party DIP Switch Configuration

90-1538

LOCAL

PRIMARY/SECONDARY

EXTERNAL

SYSTEM SETUP

HVAC FAN ON

VENT-TIMED

VENT-AUTO

PRIMARY

HVAC FAN OFF

ON

1234

SWITCH FLOA

TO

DT

SENSO

R

R
C

W

Y

G

A+
B

DE

H

REMOT

E

HV

AC EQUI

P

VEN
T

Cf
Gs
Gh
W-

DH

Rf

DAMPERS

C
R

RC
RH
HC

W
W2
W3
Y
Y2
Y3

C

L

G

DH

VENT

EAC

DH

DH

HUM

HP

B

W2

W

G

O

Y2

Y

nc
com
no

EQ

DEHUMIDIFIER

CONTROL BOARD

HVAC EQUIPMENT

MODEL 8910

 HOME COMFORT CONTROL

EQUIPMENT CONTROL

MODULE

Wiring Notes:

•  DEH output(s) on control must be normally open.

IMPORTANT:

 The dehumidifier Rf and Cf terminals must be 

powered from the transformer that powers the Model 8910 Home 
Comfort Control

 or third-party control .

Third-Party Control with 2 Dehumidifier Connections

1 .  Connect one thermostat dehumidifier terminal to the Rf terminal on 

the dehumidifier control board . 

2 .  Connect the other thermostat dehumidifier terminal to the DH 

terminal on the dehumidifier control board .

Third-Party Control with 1 Dehumidifier Connection

Connect the thermostat dehumidifier terminal to the DH terminal on 
the dehumidifier control board .

SEQUENCE Of OPERATION

•  When the measured humidity is greater than the humidity setting on the Model 8910 Home Comfort Control

 or other Third-Party Control, the 

dehumidifier damper output turns on, the dehumidifier blower turns on, and the green Status LED on the dehumidifier flashes .

•  Three seconds after the dehumidifier blower turns on, the compressor turns on and the green Status LED switches to solid illumination.
•  When the measured humidity falls below the setting on the Model 8910 Home Comfort Control

 or other Third-Party Control, the dehumidifier 

damper output turns off and the dehumidifier blower and compressor turn off along with the green Status LED .

fIGURE 31 – Model 8910  

Home Comfort Control

 Wiring

90-1537

21

Summary of Contents for 1750A

Page 1: ...disconnected until installation service is completed 3 Sharp edges may cause serious injury from cuts Use care when cutting plenum openings and handling ductwork 4 Dropping may cause personal injury o...

Page 2: ...SINGLE ZONE DUCTED TO HVAC SYSTEM see page 7 SINGLE ZONE NOT DUCTED TO HVAC SYSTEM see page 9 TWO ZONE PRIMARY AND SECONDARY ZONED see page 11 In a Single Zone Ducted to HVAC System installation the d...

Page 3: ...non condensing Filter MERV 8 washable Compressor Minimum Off Time 3 minutes Compressor Minimum On Time 3 minutes Airflow 1750A External Static Pressure Airflow 0 0 w c 380 CFM 0 4 w c 310 CFM 0 6 w c...

Page 4: ...6mm Minimum Clearance for Filter and Front Panel Removal 20 in 508mm Minimum Clearance for Filter Removal 6 in 152mm Minimum Clearance for Filter Removal Air Inlet 8 in Round Collar Service Access Pan...

Page 5: ...OUTLET 4 MIN BACKFLOW DAMPER CAUTION Only install damper on outlet Dehumidifier will not function if damper is installed on inlet GENERAL DUCTWORK RECOMMENDATIONS When ducted to the HVAC supply the ou...

Page 6: ...drip pan located below the coil CAUTION 1 Drain trap must be primed with water before use 2 A condensate pan with a float switch is required in attic installations High Side Low Side Drain Outlet Dra...

Page 7: ...ly Closed Float Switch Grille Model 76 Control Model 8910 Home Comfort Control Third Party Control Figure 9 Single Zone Ducted to HVAC System Basement Installation AIR IS PULLED FROM RETURN DUCT DEHUM...

Page 8: ...d to the supply side The Alternate Installation see Figure 12 minimizes re evaporation of moisture off the cooling coil Attic Installation Notes The dehumidifier must be installed in a secondary conde...

Page 9: ...n and the green Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Stat...

Page 10: ...14 Leave the LOCAL EXTERNAL switch in the LOCAL position if using the dehumidifier s onboard control If installing a separate control see MODEL 76 EXTERNAL CONTROL on page 19 MODEL 76 REMOTE CONTROL o...

Page 11: ...ary Zone Required Components Duct Work 18 22 AWG Wire Grilles 2 Aprilaire Model 6508 8 Normally Closed Damper 2 Aprilaire Model 6608 8 Normally Open Damper 24 VAC Transformer 40VA min for Dampers NOTE...

Page 12: ...hrough the unit dehumidified and circulated solely by the dehumidifier blower CYCLE PERIOD This determines how frequently the dehumidifier will sample the air to check the humidity level Set to 1 hour...

Page 13: ...n Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the green Status LED begins flashing as the dehumidifier begins Secondary...

Page 14: ...unction in Air Cycling mode activating the HVAC blower to cycle air through the home based on the Cycle Period and Cycle Time Required Components Aprilaire Model 6506 6 Normally Closed Damper 24 VAC T...

Page 15: ...QUIREMENTS See page 17 for outdoor temperature sensor installation 1 The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 ASHRAE Airflow in CFM House Area in Sq Ft x 0 01 Number of Bedr...

Page 16: ...d a fully opened damper Rigid pipe values are based on 6 duct two 90 elbows and a fully open damper In both cases the air intake is through a metal vent hood with inlet screen Airflow may need to be a...

Page 17: ...requirement is met ventilation will not occur until the next cycle period SETTING DIP SWITCHES CYCLE TIME TO MEET VENTILATION REQUIREMENTS Figure 22 VENT TIMED DIP Switch Settings 90 1538 ON 1 2 3 4 4...

Page 18: ...s active The dew point of the air is measured 3 minutes after the dehumidifier blower is turned on and every 15 seconds while the blower is running If the dew point of the air is above the setting on...

Page 19: ...EM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT THERMOSTAT G R C G...

Page 20: ...90 1538 LOCAL PRIMARY SECONDARY EXTERNAL SYSTEM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CO...

Page 21: ...Rf DAMPERS C R RC RH HC W W2 W3 Y Y2 Y3 C L G DH VENT EAC DH DH HUM HP B W2 W G O Y2 Y nc com no EQ DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT MODEL 8910 HOME COMFORT CONTROL EQUIPMENT CONTROL MODULE...

Page 22: ...structions for the Model 76 Control Model 8910 Home Comfort Control or Third Party Control for setting adjustments Figure 33 Control Knob Setpoint 90 1327 EXAMPLE At an indoor temperature of 75 F and...

Page 23: ...rd Turn the dehumidifier back on and increase the dryness level setting on the Model 76 If the dehumidifier turns on the problem is with the wiring between the dehumidifier and control 3 If the dehumi...

Page 24: ...tage across the R C terminals on the dehumidifier control board Voltage should be 18 VAC 30 VAC Incorrect wiring Verify wiring and connections between the thermostat HVAC and dehumidifier HVAC fan ope...

Page 25: ...ly included with Model 1710A only 1 4863 12 LED Control Door 1 4864 No Part Description Qty Ctn Part No 13 10 VA Transformer 1 5262 14A Capacitor 60MF 1770A 1 5255 14B Capacitor 55MF 1710A 1750A 1 492...

Page 26: ......

Page 27: ......

Page 28: ...P O Box 1467 Madison WI 53701 1467 Phone 800 334 6011 Fax 608 257 4357 www aprilairepartners com 10009845 5 12 B2205733B Printed in U S A 2012 Aprilaire A division of Research Products Corporation...

Page 29: ......

Reviews: