background image

SINGlE ZONE – NOT DUCTED TO HVAC SySTEM INSTAllATION 

(CONTINUED)

fIGURE 15 – Single Zone – Not Ducted to HVAC Installation

DEHUMIDIFIED SPACE

DEHUMIDIFIER

EQUIPMENT ROOM

HVAC FURNACE

DEHUMIDIFIED AIR 

IS SUPPLIED

TO DUCTED SPACE

AIR IS PULLED

FROM AREA

GRILLE WITH 8" DIA. 

DUCT COLLAR – 1750A
GRILLE WITH 10" DIA. 

DUCT COLLAR – 1770A

10’

MINIMUM

90-1536

DUCTING & WIRING

Wiring Notes:

•  If using the on-board dehumidifier control, no 

additional wiring is required .

•  If wiring to a Model 76 Control, where the control 

will be mounted in the space being dehumidified, see 
MODEL 76 EXTERNAL CONTROL section on page 19.

•  If wiring to a Model 76 Control, where the control will 

be located somewhere other than the space being 
dehumidified, see MODEL 76 REMOTE CONTROL 
section on page 20 .

•  If wiring to a Model 8910 Home Comfort Control

 

or Third-Party Control, see MODEL 8910 HOME 
COMFORT CONTROL

 OR THIRD-PARTY CONTROL 

section on page 21 .

Ducting Notes:

•  If dehumidifying a location that is noise sensitive, 

install multiple registers to reduce air velocity .

•  Airflow is approximately 500 CFM for the 1770A, and 

275 CFM for the 1750A .

•  CYCLE PERIOD: This determines how frequently the dehumidifier will sample 

the air to check the humidity level . Set to 1 hour and adjust as needed .

•  For Ventilation switch settings, see VENTILATION section beginning on page 14.
•  Leave the LOCAL/EXTERNAL switch in the LOCAL position if using the 

dehumidifier’s onboard control . If installing a separate control, see MODEL 76 
EXTERNAL CONTROL on page 19, MODEL 76 REMOTE CONTROL on page 20,  
or MODEL 8910 HOME COMFORT CONTROL

 OR THIRD-PARTY CONTROL on 

page 21 .

fIGURE 16 – Single Zone – Not Ducted to  

HVAC System, DIP Switch Settings

90-1538

ON

1234

4

3

2

1

ON

HVAC FAN OFF

PRIMARY

VENT-AUTO

VENT-TIMED

HVAC FAN ON

2 HOUR
3 HOUR

30 MIN.

1 HOUR

SYSTEM SETUP

CYCLE PERIOD

EXTERNAL

PRIMARY/SECONDARY

LOCAL

•  Sampling will occur at the end of the Cycle Period. At the onset of sampling, the dehumidifier damper output turns on, the dehumidifier blower 

turns on, and the green Status LED flashes .

•  After three minutes, the dew point of the incoming air is measured and compared to the setting on the control knob. If the dew point of the 

incoming air is above the setting, the compressor turns on and the green Status LED switches to solid illumination . If the dew point is below 
the setting, the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Status LED . 

•  The dew point of the incoming air is continuously monitored during compressor operation. When the dew point of the incoming air falls below 

the setting on the control knob, the dehumidifier damper output turns off and the dehumidifier compressor and blower turn off along with the 
green Status LED .

SEQUENCE Of OPERATION (Refer to pages 19-21 for sequence with alternate controls.)

DIP SWITCH CONfIGURATION

10

Summary of Contents for 1750A

Page 1: ...disconnected until installation service is completed 3 Sharp edges may cause serious injury from cuts Use care when cutting plenum openings and handling ductwork 4 Dropping may cause personal injury o...

Page 2: ...SINGLE ZONE DUCTED TO HVAC SYSTEM see page 7 SINGLE ZONE NOT DUCTED TO HVAC SYSTEM see page 9 TWO ZONE PRIMARY AND SECONDARY ZONED see page 11 In a Single Zone Ducted to HVAC System installation the d...

Page 3: ...non condensing Filter MERV 8 washable Compressor Minimum Off Time 3 minutes Compressor Minimum On Time 3 minutes Airflow 1750A External Static Pressure Airflow 0 0 w c 380 CFM 0 4 w c 310 CFM 0 6 w c...

Page 4: ...6mm Minimum Clearance for Filter and Front Panel Removal 20 in 508mm Minimum Clearance for Filter Removal 6 in 152mm Minimum Clearance for Filter Removal Air Inlet 8 in Round Collar Service Access Pan...

Page 5: ...OUTLET 4 MIN BACKFLOW DAMPER CAUTION Only install damper on outlet Dehumidifier will not function if damper is installed on inlet GENERAL DUCTWORK RECOMMENDATIONS When ducted to the HVAC supply the ou...

Page 6: ...drip pan located below the coil CAUTION 1 Drain trap must be primed with water before use 2 A condensate pan with a float switch is required in attic installations High Side Low Side Drain Outlet Dra...

Page 7: ...ly Closed Float Switch Grille Model 76 Control Model 8910 Home Comfort Control Third Party Control Figure 9 Single Zone Ducted to HVAC System Basement Installation AIR IS PULLED FROM RETURN DUCT DEHUM...

Page 8: ...d to the supply side The Alternate Installation see Figure 12 minimizes re evaporation of moisture off the cooling coil Attic Installation Notes The dehumidifier must be installed in a secondary conde...

Page 9: ...n and the green Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the dehumidifier blower turns off along with the green Stat...

Page 10: ...14 Leave the LOCAL EXTERNAL switch in the LOCAL position if using the dehumidifier s onboard control If installing a separate control see MODEL 76 EXTERNAL CONTROL on page 19 MODEL 76 REMOTE CONTROL o...

Page 11: ...ary Zone Required Components Duct Work 18 22 AWG Wire Grilles 2 Aprilaire Model 6508 8 Normally Closed Damper 2 Aprilaire Model 6608 8 Normally Open Damper 24 VAC Transformer 40VA min for Dampers NOTE...

Page 12: ...hrough the unit dehumidified and circulated solely by the dehumidifier blower CYCLE PERIOD This determines how frequently the dehumidifier will sample the air to check the humidity level Set to 1 hour...

Page 13: ...n Status LED switches to solid illumination If the dew point is below the setting the dehumidifier damper output turns off and the green Status LED begins flashing as the dehumidifier begins Secondary...

Page 14: ...unction in Air Cycling mode activating the HVAC blower to cycle air through the home based on the Cycle Period and Cycle Time Required Components Aprilaire Model 6506 6 Normally Closed Damper 24 VAC T...

Page 15: ...QUIREMENTS See page 17 for outdoor temperature sensor installation 1 The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 ASHRAE Airflow in CFM House Area in Sq Ft x 0 01 Number of Bedr...

Page 16: ...d a fully opened damper Rigid pipe values are based on 6 duct two 90 elbows and a fully open damper In both cases the air intake is through a metal vent hood with inlet screen Airflow may need to be a...

Page 17: ...requirement is met ventilation will not occur until the next cycle period SETTING DIP SWITCHES CYCLE TIME TO MEET VENTILATION REQUIREMENTS Figure 22 VENT TIMED DIP Switch Settings 90 1538 ON 1 2 3 4 4...

Page 18: ...s active The dew point of the air is measured 3 minutes after the dehumidifier blower is turned on and every 15 seconds while the blower is running If the dew point of the air is above the setting on...

Page 19: ...EM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT THERMOSTAT G R C G...

Page 20: ...90 1538 LOCAL PRIMARY SECONDARY EXTERNAL SYSTEM SETUP HVAC FAN ON VENT TIMED VENT AUTO PRIMARY HVAC FAN OFF ON 1 2 3 4 MODEL 76 DAMPERS Rf DH W Gh Gs Cf VENT HVAC EQUIP REMOTE DEH B A DEHUMIDIFIER CO...

Page 21: ...Rf DAMPERS C R RC RH HC W W2 W3 Y Y2 Y3 C L G DH VENT EAC DH DH HUM HP B W2 W G O Y2 Y nc com no EQ DEHUMIDIFIER CONTROL BOARD HVAC EQUIPMENT MODEL 8910 HOME COMFORT CONTROL EQUIPMENT CONTROL MODULE...

Page 22: ...structions for the Model 76 Control Model 8910 Home Comfort Control or Third Party Control for setting adjustments Figure 33 Control Knob Setpoint 90 1327 EXAMPLE At an indoor temperature of 75 F and...

Page 23: ...rd Turn the dehumidifier back on and increase the dryness level setting on the Model 76 If the dehumidifier turns on the problem is with the wiring between the dehumidifier and control 3 If the dehumi...

Page 24: ...tage across the R C terminals on the dehumidifier control board Voltage should be 18 VAC 30 VAC Incorrect wiring Verify wiring and connections between the thermostat HVAC and dehumidifier HVAC fan ope...

Page 25: ...ly included with Model 1710A only 1 4863 12 LED Control Door 1 4864 No Part Description Qty Ctn Part No 13 10 VA Transformer 1 5262 14A Capacitor 60MF 1770A 1 5255 14B Capacitor 55MF 1710A 1750A 1 492...

Page 26: ......

Page 27: ......

Page 28: ...P O Box 1467 Madison WI 53701 1467 Phone 800 334 6011 Fax 608 257 4357 www aprilairepartners com 10009845 5 12 B2205733B Printed in U S A 2012 Aprilaire A division of Research Products Corporation...

Page 29: ......

Reviews: