DIMENSIONS
"H"
6-3/8
6-3/8
6-3/8
7-3/8
7-3/8
7-3/8
6-3/8
6-1/4
6-1/4
7
7
7
"W"
6-1/4
6-1/4
250
600
400
500
350
300
325
275
200
150
175
100
125
85
45
65
75
55
40
SIZE
35
NOTES:
1.
WEIGHT OF STACK MUST BE SUPPORTED FROM FLOOR
OR BUILDING STRUCTURE. DO NOT SUPPORT STACK
FROM INDUCED DRAFT FAN.
2.
RECOMMENDED STACK MATERIAL IS 14 GAGE SERIES
400 STAINLESS STEEL, CONTINUOUSLY BUTT WELDED
EXHAUST STACK.
3.
PITCH HORIZONTAL RUNS UPWARD
1
4
INCH PER FOOT
TOWARD OUTLET FOR CONDENSATE DRAINAGE. SUPPORT
HORIZONTAL RUNS AS REQUIRED TO PREVENT SAGGING.
4.
FOR NON HIGH TURNDOWN BURNERS, WHENEVER USING
SIDE WALL VENTING A DRAIN LINE SHOULD BE ADDED
TO THE BOTTOM OF THE EXHAUSTER HOUSING FOR
CONDENSATE REMOVAL.
H X W
8"-10"MIN
24"MIN
RAIN
DIVERTER
SIDE WALL VENTING
EXHAUSTER
APPROVED SIDE
WALL VENT DEVICE
H X W
BUILDING WALL
BUILDING WALL
ALTERNATE SIDE
WALL DESIGN
APPROVED SIDE
WALL VENT DEVICE
SEE NOTE 4
EXHAUSTER
SEE NOTE 4
Summary of Contents for GAS-FIRED HEATERS
Page 6: ... 6 ...
Page 7: ... 7 ...
Page 8: ... 8 ...
Page 9: ... 9 ...
Page 13: ... 13 ...
Page 24: ... 24 TYPICAL SEQUENCE FOR MODULATING THERMOSTAT WITH 135 OHM CONTROLS ...
Page 25: ... 25 TYPICAL SEQUENCE FOR MODULATING THERMOSTAT WITH 4 20 mA CONTROLS ...
Page 64: ...4830 Transport Drive Dallas TX 75247 Phone 214 638 6010 Fax 214 905 0806 www appliedair com ...