7
Getting Started
⚠
CAUTION
Always use a grounded outlet that meets minimum voltage supply requirements for industrial
equipment. Do not use with portable power generators.
⚠
CAUTION
Always open valves slowly for safety, and to check for leaks.
⚠
CAUTION
The G5Twin is equipped with a 550psi (38.6 kg/cm
2
) pressure shut off switch to protect the
machine from damage. This does not prevent overfilling of the storage container.
(See Page 6)
G5TWIN OPERATION MANUAL
© 2016 APPION INC. - ALL RIGHTS RESERVED
CHECKING YOUR RECOVERY EQUIPMENT
ACCESSORY EQUIPMENT
Before connecting or operating the G5Twin, verify that the G5Twin will be able to operate properly:
•
Check that the
debris screen at the inlet fitting is clean before starting every job. This screen prevents
damage to the machine that may get past the inline filter. When pumping dirty/used refrigerant, this screen
may quickly clog and slow the process when used without an inline filter.
•
Verify the
power source provides adequate voltage at the machine while it is running (within 10% of the
rated power). When using an extension cord, follow the sizing guidelines on Page 4.
Review the information for Care and Maintenance on Page 17 regularly to ensure optimal performance.
Additional equipment may be used to connect the G5Twin to the system you are recovering refrigerant from.
Verify operational details and safety information from the manufacturers of other equipment before use.
•
.
A leaking hose may cause venting of refrigerant, and may introduce atmospheric air or other
contaminants into the recovered refrigerant. Examine the
gaskets on each hose to ensure they are intact,
checking for any damage or wear that may lead to leaks.
•
Use the shortest length of
3/8”-diameter hoses possible on every connection. IMPORTANT:
Do not use
“quick disconnect” or “auto-shutoff” hoses
for refrigerant recovery, as this can bring the recovery to a halt.
•
Use
Valve Core Removal Tools with a ball valve (such as Appion MegaFlow VCT) to remove all “Schrader”-
type
access valve cores
from the System access fittings. This prevents restrictions that would otherwise
limit the performance of the G5Twin and/or cause overheating of the recovery cylinder. See Page 15 for
more information.
•
The
recovery cylinder should have extra capacity beyond the amount you intend to recover. For maximum
recovery speeds, use a recovery cylinder that is already evacuated (500 microns or better).
Note: new
recovery cylinders may not be sufficiently evacuated - always verify before use.
•
Check your
refrigerant scale with a known weight to ensure that is operating correctly. A malfunctioning
scale may not alert you to the amount of refrigerant in the storage container.
•
Examine your
external manifold gauges for
proper valve operation and calibration
of the gauges. Contact
the manifold gauge manufacturer for instructions in this process.
•
Use a
new inline filter dryer as shown
when pumping dirty refrigerant
. Replace the filter dryer after each
use. If the filter has exceeded its capacity, this may affect the performance of the machine.
•
Use a
sight glass to
verify liquid flow
. This can also be useful for troubleshooting purposes. Make sure that
the sight glass is in good condition and does not leak.
⚠
CAUTION