MANAGEMENT
SYSTEMS
Assessed to ISO 9001:2008
Cert/LPCB ref. 010
Assessed to ISO 14001:2004
Cert/LPCB ref. 010 EMS
MANAGEMENT
SYSTEMS
Cert/LPCB ref. 010
PRODUCT
CERTIFICATION
Apollo Test Set - User Manual
25
How do I use Programmer mode?
Programmer mode is used with the detector base provided. In this mode only CoreProtocol is used. The detector
mounting base with an XPERT8 address card with a pre-defined address of 1.
The detector mounting base will accept all detector types - Series 90, XP95, Discovery and Soteria. The detector base is
connected to the test set unit using the supplied cables into the appropriate connections on the top of the unit.
The Test Set can also be used with manual call points, switch monitors, input/output devices and sounders.
Insert the required device into the
detector base.
Tap the ‘Programmer mode’ tab on the
Home screen.
The programmer mode splash screen
appears.
Note:
If no device is detected ‘Device not fitted’
appears on the splash screen.
The Programmer mode splash screen shows this information:
1
2
3
4
5
6
7
1
Currently fitted device information
1. Device type description
2. Serial number in hex XXXX-XXXXXXXXX (MSB to LSB)*
3. Date of manufacture - month name, year)**
2
Live analogue value
3
Drift value - if device is enabled for this
4
Test buttons - only enabled if device will allow these tests.
• Grey button - deactivated
• Blue button - activated
5
Sensor status*
6
Settings ** - available options depend on device type code
7
Restore to factory defaults button**
Note:
* Soteria devices only, ** Soteria and Discovery devices only
Summary of Contents for SA7800-870APO
Page 1: ...Apollo Test Set User Manual 1 Apollo Test Set User Manual...
Page 45: ...Apollo Test Set User Manual 45 Appendix C Loop supply from direction OUT...
Page 47: ...Apollo Test Set User Manual 47 Appendix E Earth fault location search...
Page 49: ...Apollo Test Set User Manual 49 Appendix G Line Voltages...