4.4 Installation Position
4.5 Installation Procedure
4.5.1 Hole Drilling
1. Determine the four mounting spots for plugging the expansion bolts as outlined in the diagram
below. The depth and internal diameter of each drilled hole is 10 mm and in the range of 55
to 60 mm, respectively.
1. Install the solar inverter in a vertical position, and ensure the con-
nection ports are located underneath or face down.
2. It is prohibited to install the inverter obliquely towards the front.
3. It is prohibited to install the inverter horizontally.
4. It is prohibited to install the inverter obliquely towards one side.
5. It is suggested to install the inverter at a mounting height that ke-
eping the LED screen at the same level with the user's eyes so as
to facilitate the ease of operation and data reading.
290.0mm
400.0mm
Description
Please install the solar inverter in a place which is stable and solid enough to bear the
dead weight of the inverter for long term.
Structural diagram of an e
b
:
xpansion olt
1
2
3
4
Tools to prepare: Percussion drill, rubber hammer, screw driver, wire stripper and multimeter.
Ensure there is no interference by other electrical equipment around the solar inverter.
Smart MTL Series 3-Phase Inverter User Manual--Installation
11/38
PROFESSIONAL
INNOVATIVE BRANDING
SERVICE