PacMAGIC HEAT PUMP
37
Water Pump
F40 Water Pump Select
0
–
1
1
-
0: water pump is not enable
1: water pump is enable
F41
Water pump starts time
before compressor starts
1
–
10
3
min
F42
Water pump stops time
after compressor stops
0
–
10
3
min
F43 Water pump stop time
OFF
1 – 99
60
min
F44 Water pump run time
OFF
1 – 10
5
min
Alarm
F50 External alarm mode
3
3
-
3: always closed, unlocked
F51 External alarm mode
3
3
-
3: always closed, unlocked
F52 External alarm mode
3
3
-
3: always closed, unlocked
F59
Buzzer alarm sound
duration
OFF,
0.1 -- 10,
On
OFF
min
Off: No alarm sound
On: Alarm sound is always
on until pressing any key
RTC
F60 Set the RTC time
00:00—23:59
-
-
F61 Period 1 start time
00:00—23:59
OFF
05
:
00
-
OFF means not using
F62 Period 1 end time
00:00—23:59
OFF
07
:
00
-
F63 Period 2 start time
00:00—23:59
OFF
16
:
00
-
F64 Period 2 end time
00:00—23:59
OFF
18
:
00
-
F65 Period 3 start time
00:00—23:59
OFF
22
:
00
-
F66 Period 3 end time
00:00—23:59
OFF
00
:
00
-
F69 Run Mode
0/1
0
-
0
:
Automatic
1
:
Economical
F80 Password
OFF
0001 -- 9999
OFF
-
OFF means no password
0000 means clearing
password
System
setting
F81 Temperature unit
C/F
C
-
C:
Centigrade
F: Fahrenheit
F85
Display accumulative
running time
-
-
hour
F86
Accumulative running
time reset
-
-
-
F87 Probation time
OFF
1 -- 9999
OFF
hour
The controller will stop if the
accumulative time is over
probation time, and show the
alarm code “A99”.
OFF means no probation
time
F98 Reserved
Testing
F99 Auto Test
This function can attract all relays in turn, and please don’t use it
when the controller is running!
End Exit
en
gli
sh
Summary of Contents for 60298
Page 2: ......
Page 11: ...11 ATTENTION POMPE CHALEUR PacMAGIC fran ais...
Page 29: ...ATTENTION PacMAGIC HEAT PUMP english 29...
Page 47: ...ATENCI N BOMBA DE CALOR PacMAGIC espa ol 47...
Page 65: ...deutsch ACHTUNG 65...
Page 79: ...ERROR syntaxerror OFFENDING COMMAND ztokenexec_continue STACK filestream...