27
code HG0141.00GB ed.A-2008
LRP - RAPID PRO and LK - KONDENSA
LRP and LK WARM AIR HEATER
L
max
HG140.00_IM_023
L
max
HG140.00_IM_022
HG140.00_IM_033
HG140.00_IM_034
Vertical B23 terminal
Open combustion circuit, combustion air intake from the room
and exhaust to the outdoor. Standards UNI-CIG 7129 and 7131
require the provision of suitable vents on the walls.
NOTE: In this configuration, combustion air intake re
-
quires an IP20 safety meshing to be fitted, which must
prevent a solid object with a diameter higher than 12mm
from going through; at the same time, the meshing must
have holes larger than 8mm.
L
max
of the pipe routing made with the Ø shown, excluding the
terminal.
The terminal consists of:
•
Adaptor from LRP or LK outlet to exhaust Ø (where nec-
essary);
•
Roof-mounted terminal, only windproof exhaust.
Ø80 pipes and bends: TB23-08-VSW
Mod. LK
020
034
045
065
080
105
L
max
[m]
30
30
30
15
-
-
Mod. LRP
018
028
035
045
055
075
102
L
max
[m]
30
30
30
30
25
10
-
Ø100 pipes and bends: TB23-10-VSW + G15815-08-10 (ec-
centric adaptor only for mod. LK020-065 and LRP018-075)
Mod. LK
020
034
045
065
080
105
L
max
[m]
-
-
-
30
30
20
Mod. LRP
018
028
035
045
055
075
102
L
max
[m]
-
-
-
-
30
30
25
Fumes OUT
Fumes OUT
Installing the terminals
The LRP and LK heaters are fitted with a top and bottom pro
-
vision for air inlet and fume exhaust.
According to installation requirements, the terminals can be
fitted at the back or at the top.
The exhaust and drainage castings are normally installed on
the back of the machine; should it be necessary to use the top
outlets, remove the castings from the rear section and the covers
(with their seals) from the top holes, fit the castings again in
their seats on the upper side and the covers (with seals) on the
unused rear holes, in order to ensure their tightness.
ATTENTION: When changing the intake/exhaust side,
pay attention to the mounting direction of the terminals.
(UP arrow) DO NOT INVERT the flue outlet terminal with
the air intake terminal.
NOTE: The terminals are supplied with silicone seals;
on request, only for LK models, a kit with EPDM seals
can be requested.
Fume exhaust and upper air intake
Fume exhaust and rear air intake