26
code HG0141.00GB ed.A-2008
LRP - RAPID PRO and LK - KONDENSA
LRP and LK WARM AIR HEATER
LRP models
018
028
035
045
055
075
102
Pressure available at the exhaust
80
100
120
120
130
140
140
[Pa]
Component
Pressure drop [Pa]
Code
Ø80 SMOOTH PIPE [l=1m]
0.8
1.9
3.0
4.6
5.9
10.7
18.2
G15820-08-XXX
BEND Ø80 WIDE RADIUS 90°
1.3
3.3
5.1
7.7
10.0
18.1
31.0
G15810-08-90
BEND Ø80 WIDE RADIUS 45°
0.6
1.5
2.4
3.6
4.7
8.5
14.6
G15810-08-45
Ø80 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
7.1
17.1
26.1
38.2
50.5
88.9
149.8
TC13-08-HC1
Ø80 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
7.2
18.9
30.6
47.5
65.6
125.6
226.4
TC33-08-VC1
Ø80 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
0.0
0.0
0.2
0.4
0.8
2.1
-
TB23-08-VSW
Ø100 SMOOTH PIPE [l=1m]
0.0
0.7
1.0
1.6
2.1
3.6
6.5
G15820-10-XXX
BEND Ø100 WIDE RADIUS 90°
0.0
1.3
2.0
3.2
4.1
7.3
13.1
G15810-10-90
BEND Ø100 WIDE RADIUS 45°
0.0
0.6
0.9
1.5
1.9
3.3
5.9
G15810-10-45
Ø100 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
3.8
9.1
14.6
22.7
31.5
61.3
112.0
TC13-10-HC2
Ø100 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
3.0
7.7
12.6
20.2
28.4
56.5
105.0
TC33-10-VC2
Ø100 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
-
0.1
0.3
0.7
1.2
2.9
6.2
TB23-10-VSW
SMOOTH Ø130 PIPE [l=1m]
0.0
0.2
0.3
0.5
0.6
1.1
1.8
G15820-13-XXX
Ø130 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
3.1
3.7
4.7
6.5
8.7
17.0
32.4
TC13-13-HC5
Ø130 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
1.1
2.8
4.6
7.2
10.0
19.3
35.3
TC33-13-VC5
Ø130 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
-
0.1
0.3
0.7
1.2
2.9
6.2
TB23-13-VSW
ADAPTOR Ø80/100
0.2
0.5
0.8
1.2
1.7
3.4
-
G15815-08-10
ADAPTOR Ø100/80
0.2
0.5
0.8
1.2
1.7
3.4
6.4
G15815-10-08
ADAPTOR Ø100/130
0.1
0.3
0.6
0.9
1.3
2.7
5.0
G15815-10-13
ADAPTOR Ø130/100
0.1
0.2
0.4
0.6
0.8
1.7
3.1
G15815-13-10
COMBUSTION AIR UPTAKE ONLY
Ø80 HORIZONTAL AIR UPTAKE ONLY
0.5
1.5
2.6
4.3
6.1
12.3
-
TB23-08-HS0
Ø100 HORIZONTAL AIR UPTAKE ONLY
0.3
0.8
1.3
2.1
2.9
5.7
10.4
TB23-10-HS0
LK models
020
034
045
065
080
105
Pressure available at the exhaust
80
90
100
120
120
120
[Pa]
Component
Pressure drop [Pa]
Code
Ø80 SMOOTH PIPE [l=1m]
0.8
2.0
2.8
5.8
8.8
12.4
G15820-08-XXX
BEND Ø80 WIDE RADIUS 90°
1.3
3.4
4.8
9.8
14.9
21.1
G15810-08-90
BEND Ø80 WIDE RADIUS 45°
0.6
1.6
2.2
4.6
7.0
9.9
G15810-08-45
Ø80 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
9.0
25.3
34.3
70.2
103.4
144.9
TC13-08-HC1
Ø80 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
9.2
29.6
42.0
95.9
149.2
218.2
TC33-08-VC1K
Ø80 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
-
0.1
0.4
1.4
2.7
4.4
TB23-08-VSW
Ø100 SMOOTH PIPE [l=1m]
0.3
0.7
1.0
2.1
2.9
4.4
G15820-10-XXX
BEND Ø100 WIDE RADIUS 90°
0.5
1.4
1.9
4.1
5.8
8.8
G15810-10-90
BEND Ø100 WIDE RADIUS 45°
0.2
0.6
0.9
1.9
2.6
4.0
G15810-10-45
Ø100 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
4.7
14.1
20.0
46.5
73.1
107.9
TC13-10-HC2
Ø100 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
3.8
12.2
17.7
42.5
67.8
101.0
TC33-10-VC2K
Ø100 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
-
0.3
0.6
2.0
3.7
5.9
TB23-10-VSW
SMOOTH Ø130 PIPE [l=1m]
0.1
0.2
0.3
0.6
0.8
1.2
G15820-13-XXX
Ø130 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX
3.1
4.6
5.9
12.7
20.5
31.1
TC13-13-HC5
Ø130 ROOF-MOUNTED TERMINAL FROM SEPARATE TO COAX
1.4
4.4
6.3
14.7
23.0
34.0
TC33-13-VC5K
Ø130 ROOF-MOUNTED TERMINAL, WINDPROOF EXHAUST ONLY
-
0.3
0.6
2.0
3.7
5.9
TB23-13-VSW
ADAPTOR Ø80/100
0.2
0.7
1.2
2.6
4.1
6.2
G15815-08-10
ADAPTOR Ø100/80
0.2
0.7
1.2
2.6
4.1
6.2
G15815-10-08
ADAPTOR Ø100/130
0.2
0.6
0.9
2.0
3.2
4.8
G15815-10-13
ADAPTOR Ø130/100
0.1
0.4
0.6
1.2
2.0
3.0
G15815-13-10
COMBUSTION AIR UPTAKE ONLY
Ø80 HORIZONTAL AIR UPTAKE ONLY
0.6
2.5
4.1
9.2
14.8
22.2
TB23-08-HS0
Ø100 HORIZONTAL AIR UPTAKE ONLY
0.4
1.3
2.0
4.3
6.8
10.0
TB23-10-HS0
NOTE: Values calculated on the flue gas mass flow rate achieved with natural gas G20.