background image

Revision 1.1 

04/2019 

 

Document No. D137-011

 

 

 

 

 

 

Page 

2

 of 

4

 

 

MODULE INSTALLATION 

The  PMIO  Scanner  is  a  standard  single  slot  ControlLogix  module  and  fits  directly  into  any  ControlLogix 
chassis. All required power for the module is derived from the ControlLogix backplane. On the front of the 

module are 2 x 3-way communication connectors for the redundant I/O Link to the Honeywell IOP Rack(s). 
 

 

 

LED 

Description 

Ok 

The  module  LED  will  provide  information  regarding  the  system-level  operation  of  the 

module. If the LED is red, then the module is not operating correctly. For example, if the 

module application firmware has been corrupted or there is a hardware fault the module will 
have a red Module LED.  

 
If the LED is green (flashing), then the module has booted and is running correctly without 

any application configuration loaded. 

 
If  the  LED  is  green  (solid),  then  the  module  has  booted  and  is  running  correctly  with 

application configuration loaded. 

A / B 

LED A represents Channel A of the I/O Link and LED B represents Channel B of the I/O Link. 

Each time a valid packet is received on a specific channel the relevant LED will flash green. 

When a corrupted packet is received the relevant LED will flash red. 

 
 

I/O LINK 

The pair of 3-way I/O Link connectors are used to connect to the TDC 3000 I/O. The details of the I/O Link 
connector are shown below. 

 

Reviews: