APAR AR602.B User Manual Download Page 12

12 

Table 8.

 List of configuration parameters

 

Parameter

 (index: name) 

Value and range of variability of the parameter

 (value: name)

 and 

description 

Default 

I. MEASURING INPUT CONFIGURATION

inCo

 submenu

 

0:

 

inP 

type of measurement input 

 

0:

 

Pt

 Pt100 sensor (RTD, -200÷850°C)

 

1:

 

ni

 Ni100 sensor (RTD, -50÷170°C) 

Pt

 

2:

 

Pt5

 Pt500 sensor 

(RTD, -200÷620°C)

 

3:

 

Pt10

 

Pt1000 sensor 

(RTD, -200÷520°C) 

4:

 

tc-J

 

thermocouple type J  

(-40 ÷ 800 ° C)

 

5:

 

tc-K

 

thermocouple type K 

(-40÷1200°C) 

6:

 

tc-S

 thermocouple type S 

(-40 ÷ 1600 ° C)

 

7:

 

tc-b

 thermocouple type B 

(300÷1800°C) 

8:

 

tc-r

 thermocouple type R  

(-40÷1600°C) 

9:

 

tc-t

 thermocouple type T 

(-25÷350°C) 

10:

 

tc-E

 thermocouple type E 

(-25÷820°C)

 

11:

 

tc-n

 

thermocouple type N  

(-35÷1300°C) 

12/13:

 

4

0-20

 4÷20 mA / 0÷20 mA current signals

 

14/15:

 

0-10

60

 0÷10 V / 0÷60 mV voltage signals 

16:

 

rES

 resistance signal 0÷2500 Ω 

1:

 

LirE

 line resistance 

(1)

 

0.00

 ÷ 

50.00

 

Ω

 

total line resistance for 2-wire RTDs and 2500 Ω sensors 

0.00

 Ω 

2:

 

cJtE

 temperature of 

thermocouple cold ends 

0:

 

Auto

  

0.1

 ÷ 

60.0

 

°

 C 

automatic or constant temperature compensation of the 
reference junction of thermocouples, 

Auto

 = 0.0 

°

°C 

Auto 

3:

 

dot

 dot 

position/resolution

 

0

 

/

 

no dot / 

0.0

 

(2)

or resolution 1/0.1°C for temperature 

(0.1°C) 

2

 / 

3

 

0.00

 /

 

0.000

 

(2)

 

4:

 

irLo

 lower limit for SP or 

the bottom of the 
indication range

  

/99.9

 ÷ 

1800

  

lower setting limit for setpoints SP (11:

 

Set1

 

÷ 

Set3

 ) 

/99.9

 

°C

 

/999

 ÷ 

9999

 

(2)

 

beginning of the scale for the 0/4mA, 0V, 0Ω input and the 
PV 

bargraph

 

5: 

irHi

 upper limit for SP 

or the top of the indication 
range 

 

/99.9

 ÷ 

1800

  

upper setting limit for setpoints

 

SP

 

(11:

 

Set1

 

÷ 

Set3

 )

 

850.0

 

°C

   

/999

 ÷ 

9999

 

(2)

 

end of scale for 20mA, 10V, 60mV, 2.5kΩ inputs and  

PV

 

bargraph 

6:

 

FiLt

 filtration 

(3)

 

1

 ÷

 

20

 

digital filtering degree (response time) 

3

 (

~0.5s) 

7:

 

cALo

 zero calibration

 

zero offset for measurements:

 

-100.0

 

÷ 

100.0

 °C

 

or 

-1000

 

÷ 

1000

 units 

(2)

 

0.0

 

°C

 

8:

 

cALG

 gain

 

85.0

 ÷ 

115.0

%

 

slope calibration (sensitivity) for measurements

 

100.0

 %

 

II. CONFIGURATION OF OUTPUTS 1

÷

(P/SSR), submenu 

out1

 ÷ 

out3

, in 3 groups 

out1

/

2

/

3

 there are the same sets of 

parameters with different indices and numbering in the names (and possibly the range of variability), description 

chapter 9

 

 
9:

 

ctY1

 control algorithm 

 

16:

 

ctY2

 

for output 2 

(

out2

23:

 

ctY3

 

for output 3 

(

out3

 
 

Note

 (for 8/9 values)

:

 

if 

[F]

/

[SET]

 or 

BIN

 with the 

0:

 

oFF

 output permanently 

switched off

 

1:

 

onof

 ON / OFF with hysteresis

 

 

onof

 

2/3/4:

 

Pid1

/

2

/

3

  PID with parameter set 1/2/3 (

chapter 9.3

)  

5/6:

 

Prgc

/

A

 

 

software - main/auxiliary output (

chapter 9.6

7:

 

hAnd 

            (manual) 

manual

 

(with 

the 

setpoint

 

set

 

 with 

 

parameter

 

67:

 

HSEt

 

and

 

pulse period of the P/SSR output, 14:

 

PEr1

/

2

3

 

8/9:

 

StbF

/

n

 

 

safety thermostat

 

STB

 

(alarm

 

with

 

memory,

 

LATCH),

 

emergency state

  

open/closed

 

(reset

 

[F]

,

 

[SET]

,

 

BIN

, chap

 

7.1

Summary of Contents for AR602.B

Page 1: ...yn ul Ga czy skiego 6 tel 22 101 27 31 853 48 56 853 49 30 e mail automatyka apar pl www apar pl USER MANUAL AR602 B AR652 B AR642 B AR682 B AR632 B AR662 B UNIVERSAL PROGRAMMABLE CONTROLLERS Version...

Page 2: ...SETPOINTS FOR OUTPUTS QUICK ACCESS MENU 17 9 2 ANALOG OUTPUT mA V 17 9 3 PID TUNING 18 9 4 AUTOMATIC SELECTION OF PID PARAMETERS 19 9 5 PID PARAMETERS CORRECTION 20 9 6 PROGRAMMED WORK CHARACTERISTIC...

Page 3: ...F CONTROLLERS ACCESSORIES AND KIT CONTENTS control and supervision of temperature and other physical values humidity pressure flow level velocity etc converted into a standard electrical signal config...

Page 4: ...input type range of indications for analogue inputs options of control alarms display communication access and other configuration parameters access to configuration parameters protected by a user s...

Page 5: ...ure 0 1 C or 1 C programmable with parameter 3 dot Indications range resolution for analog inputs maximum 1999 9999 programmable Decimal point position for analog inputs programmable 3 dot in the rang...

Page 6: ...ply circuit and relay outputs 50 V for the remaining input and output circuits and communication interfaces insulation resistance 20 M altitude above the sea level 2000 m 5 HOUSING DIMENSIONS AND ASSE...

Page 7: ...input universal 14 15 16 P1 or SSR1 relay output 14 15 for AR602 B P2 or SSR2 output 14 15 17 18 P2 or SSR2 relay output for AR602 B P1 or SSR1 output 19 20 P3 or SSR3 relay output except AR602 B USB...

Page 8: ...on the display board and carefully slide the board out of the mounting sockets connectors for signal cables power supply and relay outputs are available lead the electric wires into the housing throu...

Page 9: ...5s chap 7 1 and 8 F not available in AR602 B activation of the function selected with parameter 64 FunF pressing longer than 1 5 seconds description in chapters 7 1 and 8 UP DOWN SET simultaneously o...

Page 10: ...ive level short circuit or 0 8V Moreover BIN has priority higher than the F and SET keys Activating or stopping the function is signaled by appropriate messages on the lower display described in Table...

Page 11: ...ault value of a parameter description of the function in chapter 7 points b and c confirm the changed value of the parameter with the SET key or cancel it with the F or UP DOWN keys pressing UP DOWN o...

Page 12: ...or the bottom of the indication range 99 9 1800 lower setting limit for setpoints SP 11 Set1 Set3 99 9 C 999 9999 2 beginning of the scale for the 0 4mA 0V 0 input and the PV bargraph 5 irHi upper lim...

Page 13: ...D software main output STB LATCH and step adjustment servo 2 for PID software main output and servo algorithms only heating inversed and cooling direct characteristics apply 3 Values 4 7 i e in relati...

Page 14: ...Fto1 2 3 output emergency state for missing damaged sensor signal input or outside the measuring range 0 noCh no change 1 oFF disabled 2 on enabled 3 hAnd manual mode with a set output signal level pa...

Page 15: ...0 units min 2 1 0 C min 50 55 60 tiM1 2 3time for stage 1 2 3 0 1440min duration of the segment for the stage with countdown 60 min 51 56 61 PSE1 2 3control algorithm for step 1 2 3 1 onof ON OFF with...

Page 16: ...graph for mA V output 8 barP PV bargraph measurement in the range irLo 5 irHi con1 VIII COMMUNICATION OPTIONS FOR RS485 AND ETHERNET submenu trAn description in chapters 11 11 5 74 r4br speed for RS48...

Page 17: ...possibilities offered by the program control chapter 9 6 A detailed description of configuration of the operation of outputs is included in chapters 9 1 9 7 The default factory configuration is as fol...

Page 18: ...adjust the settings chapter 9 5 The PID control for a given control output is active when one of the three sets of PID parameters is selected with the parameter ctY1 2 3 description in chapter 8 Table...

Page 19: ...ng sudden changes of the measured value PV or the setpoint SP The choice of the parameter selection method depends on the nature of the initial conditions For a stabilized controlled quantity the step...

Page 20: ...stage 1 2 3 operates in accordance with the control parameters of the assigned setpoint SP 1 2 3 description in Table 8 point II A program can be assigned to any of the control outputs 1 2 3 with para...

Page 21: ...period for output 2 parameter 21 Per2 Sample configuration ON OFFfor heatingwith a set temperature of 50 C and a valve opening closing time of 100s output 1 parameters Table 8 point II group out1 ctY...

Page 22: ...mode on off F SET BIN function chapter 7 1 Pr 1 2 3 PEnd process controller function ramping on output 1 2 3 chapter 9 6 Stb1 2 3 STB LATCH alarm for outputs 1 2 3 cleared by F SET BIN with the functi...

Page 23: ...es not block the ports and applications used e g ARSOFT CFG The unique MAC EUI 48 hardware address of the controller Ethernet interface is available in ARSOFT CFG Parameters Communication options and...

Page 24: ...arameters used by this service such as the TCP port number are described in chapter 8 Table 8 point VIII The timeout for the MODBUS TCP transmission after which the open but unused port is closed is 6...

Page 25: ...evice function 4 or 3 register address to be read from Table 11 5 chap 11 5 number of registers to be read 1 13 CRC checksum 1 byte 1 byte 2 bytes HB LB 2 bytes HB LB 2 bytes LB HB Example 11 4 1 Read...

Page 26: ...status of outputs alarms 1 2 3 bits 0 1 2 bit 1 output enabled STB LATCH alarms for outputs 1 2 3 bits 3 4 5 bit 1 active quick manual mode for outputs 1 2 3 bits 6 7 8 bit 1 active PID tuning status...

Page 27: ...net interface EUI 48 Configuration parameters the collective list of parameters can be found in chapter 8 Table 8 Register parameter address 35 parameter index from Table 8 e g address 35 for paramete...