11
sensor or attached one other than factory programmed one. In such case, connect the appropriate sensor or
analog signal, or perform the programming of the configuration.
There are two ways to configure the parameters (manual and remote, do not use simultaneously):
1. Manually, from the membrane keyboard
placed on the front panel of the device:
- from the display mode of input measurements in the configuration menu (simultaneously press the
[UP]
and
[DOWN]
keys for longer than 1.5 sec.) If parameter 69:
PPro
=
on
(password protection is enabled) the message
CodE
will appear on display, followed by
0000
with the first digit flashing, with the
[UP]
or
[DOWN] key
enter the access password (default parameter 70:
PASS
=
1111
), to move to the next positions
and confirm the code use the
[SET]
key, to cancel the changes use the
[UP]
+
[DOWN]
or
[F]
keys,
- after entering the main configuration menu (with the message
ConF
) the upper line shows
the mnemonic name of the submenu (parameter groups:
inCo
<->
out1
<->
out2
<-> etc.), the bottom line is
dimmed or displays
none
(no module, depending on the hardware version of the controller),
- use the
[UP]
or
[DOWN]
keys to select the appropriate submenu, and then press
[SET]
to confirm
the selection (the name of the parameter is now visible on the upper line and the value on the lower line of the
display),
- the
[UP]
key takes you to the next parameter,
[DOWN]
to the previous one (eg:
inP
<->
LirE
<->
cJtE
<-> etc.,
only parameters compatible with the hardware version are available, a summary list in
Table 8
),
- to change the value of the current parameter, briefly press the
[SET]
key (flashing in edit mode),
- use the combination of
[UP]
,
[DOWN]
and
[SET] keys
to change the value of the edited parameter
(with a step of changes x1 or x10 or load the default value of a parameter, description of the function in
chapter 7
,
points b and c),
- confirm the changed value of the parameter with the
[SET]
key or cancel it with the
[F]
or
[UP]
+
[DOWN]
keys,
- pressing
[UP]
+
[DOWN]
or
[F]
again causes the return to the main configuration menu (one level up),
- exit from configuration: long press of
[UP]
+
[DOWN]
keys or automatically after approx. 2 minutes of inactivity
2. Remotely through the USB port, RS485 or Ethernet
and the ARSOFT-CFG
computer
program (
chapter 11
):
- connect the controller to the computer port, run and configure the ARSOFT-CFG application,
- after establishing the connection, the program displays the current measurement, the icon
[Tx/Rx]
signals
transmission (
chapter 7, point d
)
- setting and viewing device parameters are available in the parameter configuration window
- new parameter values must be confirmed with the
Approve changes
key
- the current configuration can be saved to a file or set with values read from the file
NOTICE:
- before disconnecting the device from the computer, use
the Disconnect the device
(ARSOFT-CFG) key
- in the absence of a response:
- check the settings in
Edit of configuration
(
Connection type
,
COM Port
,
MODBUS address of the device
, etc.)
- for USB, check whether the drivers for the serial port in the computer have been correctly installed (
see section 11
)
- disconnect for a few seconds and reconnect the regulator or the RS485 converter to the USB port of the
computer
- restart the ARSOFT-CFG and/or the computer
If there is a discrepancy between the indications and the actual value of the input signal, it is possible to tune the
zero and sensitivity to a given sensor: parameters 7:
cALo
(zero) and 8:
cALG
(sensitivity).
In order to restore the factory settings, press the
[UP]
and
[DOWN]
keys during start until the password entry
menu appears (
CodE
), and then enter the code
0112
. Alternatively, you can use the file with the default
configuration in the ARSOFT-CFG program.
!