RNO2

Annex 1. RNO2 series Modbus holding registers (part 2)

Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.

Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg/MHR

RW

Description

Supported values (dec)

Default

0x00A2 162/40163

RW

Zero adjustment for tem

-

perature data, °C × 100

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5 165/40166

RW

Zero adjustment for gas 

data, ADC

-32000...+32000 ADC units

0

0x00A6 166/40167

RW

Slope adjustment for gas 

data

1...65535

512

0x00A7 167/40168

RW

Change rate limit for gas 

data, ppm (‰ for O

2

) / s

1...32000, 0 - no limit

0

0x00A8 168/40169

RW

Integrating filter time 

constant, s 

1...32000 (seconds), 0 - no filter

0

0x00C9 201/40202

RW

Parameter tied to analog 

output 1

0-none

1- temperature

2- gas concentration

9- forced Modbus control, value set in MHR / 40204

2

0x00CA 202/40203

RW

Parameter tied to analog 

output 2

0-none

1- temperature

2- gas concentration

9- forced Modbus control, value set in MHR / 40205

2

0x00CB 203/40204

RW

Forced value for analog 

output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC 204/40205

RW

Forced value for analog 

output 2***

0...1000 (0,0%...100,0% of output scale)

0

0x00FF 205 / 40256

RW

Sensor, analog outputs, 

LED and buzzer status

bit[0]=0/1 - sensor present/absent, read-only!

bit[1]=0/1 - analog outputs deactivated/activated,

bit[2]= 0/1 - in case the sensor is absent, turn signaling off/on analog 

output1,

bit[3]=0/1 - in case the sensor is absent, turn on signaling with low 

current/high current on analog output1; if bit[2]==0 this bit will be 

ignored,

bit[4]=0/1 - in case of sensor absent, turn signaling off/on analog 

output2

bit[5]=0/1 - in case of sensor absent, turn on signaling with low 

current/high current on analog output2; if bit[4]==0 this bit will be 

ignored,

bit[6]=0/1 - current/voltage output detected on output1, read-only!

bit[7]=0/1 - current/voltage output detected on output2, read-only!

bit[8]=0/1 - LED deactivated/activated (always 0 for E2618), bit[9]=0/1 - 

buzzer deactivated/activated (always 0 for E2618)

0x0100 256 / 40257

RW

Raw temperature data, 

°C×100

signed integer, -4000...+8500 (-40,00...+85,00 °C)

0x0101 257 / 40258

R

Raw gas sensor data

ADC data 0...4095

0x0102 258 / 40259

R

Measured temperature, 

°C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103 259 / 40260

R

Gas concentration, ppm / ‰

signed integer, -32000...+32000 (ppm / ‰)

0x0105 261 / 40262

R

0% value for analog output

signed integer, -32000...+32000 (ppm / ‰)

0x0106 262 / 40263

RW

100% value for analog 

output 1

signed integer, -32000...+32000 (ppm / ‰)

0x0107 263 / 40264

RW

0% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

0x0108 264 / 40265

RW

100% value for analog 

output 2

signed integer, -32000...+32000 (ppm / ‰)

We cannot be held responsible errors in the manual/datasheet and reserve the right to correct any errors and to make product improvements, which may affect the 

accuracy of the manual/datashet, without prior notice.