RNO2

Self diagnostic

Full functionality check at startup

Warm-up time

≤ 1 min

Cable length

remote probe

Shielded cable, 2.5 or 5m

Cable connection

Screwless spring loaded terminals

Operating conditions

-30...+50 °C; 15 - 90 %rH, 

atmospheric pressure ±10%;

explosion safe (non ATEX rated) spaces

Normal ambient oxygen level

Avoid strong mechanical shock, vibrations 

or EMI

Avoid exposure to corrosive gases or 

volatile silicon containing compounds

NOTE: the sensor may exhibit sensitivity 

to chlorine.

Operating environ

-

ment

Industrial indoor and outdoor areas 

without aggressive gases or volatile silicon 

containing materials.

LCD option

Operating 

temperature

0...+50 °C

Display dimensions

72 × 36 mm

Number of digits

3.5 7-segment

Character height

14 mm

Other features

Backlight

Maximum overload

100 ppm

200 ppm

Warranty

This product is warranted to be free from 

defects in material and workmanship for a

period of one year from the date of 

original sale. 

During this warranty period

Manufacturer will, at its option, either 

repair or replace product that proves to 

be defective. 

This warranty is void if the product has 

been operated in conditions outside 

ranges specified by Manufacturer or dam

-

aged by customer error or 

negligence or if there has been an 

unauthorised modification.

The RNO2 transmitters belong to the multifunctional 

measurement instruments. 

The instruments utilise gas sensors with excellent repeatability, 

stability and long lifetime. 

The devices are supplied either in duct-mount or wall-mount version. 

The wall mount version of the device is available with remote probe. 

The remote probe is connected to the main unit with shielded cable. 

Default connection cable length is 3 m.

The RNO2 series provides two independent analog outputs OUT1 

and OUT2, user

 

selectable to 4-20 mA or 0-10 V, proportional either 

to gas concentration or temperature.

RS485 Modbus RTU digital communication interface allows easy 

instrument configuration and integration into various automation 

systems.

A design with LCD is available as an option.

Safety requirements

Always adhere to the safety provisions applicable in the country of 

use.

Do not perform any maintenance operation with the power on. 

Do not let water or foreign objects inside the device.

Operating conditions

The device should be used in explosion-safe (non ATEX -rated) indoor 

areas, without aggressive gases in the atmosphere. 

See Specification table for more details.

Installation and connections

There are no precise rules or standards to follow when installing the 

gas detectors. The following points must be taken into account:

 

-

application (air quality control or leakage detection)

 

-

properties of the space under investigation (room geometry, 

direction and velocity of air flows etc)

 

-

detected gas (relative density to air, whether the gas is flamma

-

ble, or toxiс, or oxygen displacing)

 

-

safety: strong vibrations, mechanical shock, and the sources of 

strong electromagnetic interference should be avoided

 

-

the device should be accessible for maintenance and repair.

For early leakage detection install the sensor as close as possible to 

the potential leakage sources (flanges, valves, pressure reducers, 

pumps, etc), taking into consideration other points listed above. 

For general area monitoring without definite leakage sources, the 

detectors should be distributed evenly in the room. 

For personal safety control the detectors are installed in the breath

-

ing zone (at the height of the head of people or animals). 

Recommended sensor position is vertical, pointing downwards.