RNO2

See Installation guidelines section for more information.

Step 1: Wall mount version:

 

Fix the device on a wall by screws, using cross-shaped mounting lugs 

supplied with the instrument (see dimensional drawing below).

Duct mount version:

 Cut a 36 mm diameter hole in the air duct at 

the chosen mounting place. 

Place the rubber flange aligning the holes in the flange and the 

air-duct and fix the flange with three self-tapping screws. 

Pass the sensor probe through the flange and adjust it to the 

appropriate depth.

82

80

M25

� = 28

34

200

55

230

55

80

M16

70

130

50

� = 4

Step 2:

 Unscrew four lid screws and detach the lid from the 

transmitter.

Use two M16 cable glands to pass the cables of the power supply 

and of the external devices. 

Plug the power cable and connect the analog outputs and/or digital 

interface terminals to the relevant devices according to the connec

-

tion diagram.

Controller

Power 

Supply

B

0 V

OUT1

+U

A

Control LED

OUT2

Input 2:  4 - 20 mA / 0 - 10 V

Input 2:  4 - 20 mA / 0 - 10 V

Fieldbus

0V

+24V

0V/GND

J3

SENSOR

J1 J2

J1: OUT1 type (open: 4-20 mA; closed: 0-10 V)

J2: OUT2 type (open: 4-20 mA; closed: 0-10 V)

J3: return to factory settings

The screwless quick connect spring terminals on the RNH3 series 

devices are suitable for a wide range of wires with cross-section 

0,2...1,5 mm2. We recommend to strip the wire end by 8...9 mm and 

tin it, or to use the wire end sleeves.

To connect the wire, insert the wire end into terminal hole. To dis

-

connect, push the spring loaded terminal lever, pull the wire out, and 

release the lever.

Use twisted pair cable, e.g. LiYY TP 2×2×0,5 mm2 or CAT 5, to 

connect the device to RS485 network. Use one pair for A and B wires 

and the second pair for common 0 V and power +U wires to connect 

the transmitter to Fieldbus network. Respect polarity. Overall length 

of all connections via RS485 interface should not exceed 1200 m. 

The type of each analog output can be independently changed be

-

tween 4-20 mA and 0-10 V with jumpers J1 (OUT1) and J2 (OUT2).

With closed jumper the output is 0-10 V, with open jumper the 

output is 4-20 mA.

By default both outputs OUT1 and OUT2 are assigned to gas concen

-

tration. The device has built-in temperature sensor which may be 

tied to any of the outputs.

The output assignments and scales can be changed by Modbus com

-

mands.

NOTE If you use a version with LCD, only OUT1 is available.

Step 3:

 Turn on the power. The sensor heating up may take up to five 

minutes after switching on. During this period relays, analog outputs 

and Modbus interface are off. 

A LED placed on the PCB of the device allows to control the connec

-

tion process. The LED response to different processes is presented in 

the table below.