Nov. 18

Automatikprodukter

Nitrogen Dioxide, NO

2

Gas Detector - Analogue, Modbus

4

db_nitrogen_transmitter_uk.indd

RNO2

Process

LED mode

Sensor heating period

Blinking 0.5 Hz (50% on, 50% off)

Sensor absence or 

malfunction

Blinking 0.5 Hz (90% off, 10% on)

Modbus response

The signal is modulated with short 

on-off pulses, even single Modbus cycle 

is traceable*

Normal measurement

Continuous light

Step 4:

 Make sure that the transmitter is properly fixed, the external 

devices connected, power on and control LED is constantly lit. 

Place the lid back and fix it with the screws.

The device is ready to use.

It is recommended to keep the device on constantly, except for 

periods of maintenance and calibration, deplacement etc.

Sensor probe handling

The wall mount version of the transmitter is available with remote 

probe (see drawing below for dimensions). 

The remote probe is connected to the main unit with shielded cable. 

Default connection cable length is 3 m.The sensor probes of all types 

are equipped with a hydrophobic microporous PTFE filter to protect 

the sensor from dust, dirt and water drops. 

The filter may be replaced if it gets strongly contaminated. 

To replace the PTFE filter, unscrew the M25 nut and remove the old 

filter. Place a new filter into the nut and tighten it again.

NB!

 Never stab or press the filter near its centre where the sensor is 

located since this may damage the sensor. 

The recommended orientation of sensor probe is vertical with the 

sensor tip pointing downwards. This prevents possible accumulation 

of condensed water on the sensor protection filter. 

The horizontal orientation is also suitable. Avoid upward position of 

the sensor tip.

35

80

27

36

�34max

3

120

o

�65

77

�35...36

�50

Hole

Configuring

Gas transmitters RNO2 share all functionalities of the 

multifunctional transmitter platform. 

The features and options include:

 

-

digital output change rate limiting filter

 

-

digital integrating (averaging) filter

 

-

temperature measurement channel with internal sensor

 

-

free assignment of each analog output to chosen parameter

 

-

flexible setting of analog output scales for each output

 

-

output shift and slope adjustment for calibration

 

-

Modbus controlled forced state option for analog outputs.

RNO2 can be configured through its RS485 interface by Modbus 

RTU commands. 

A standard configuration kit includes Model E1087 USB-EIA485 

converter and a software pack. 

Please contact your seller or the manufacturer for more 

information.

Return to default settings

To reset the device’s Slave ID, baudrate and sbit number to fac

-

tory settings, proceed as follows:

1.  De-energize the device

2.  Connect the J3 jumper

3.  Turn on the device

4.  De-energize the device

5.  Disconnect the J3 jumper

6.  Turn on the device

For RS485 communication interface, 

see Annex 1