-BSK4117M**1K 3/9-
■
AnyWire Type: ANF-01 Connection example
①
Power supply to the entire system
②
Local power supply/branching
DP
DN
24V
0V
POWER IN
SLAVE
POWER IN
SLAVE
LG
24V
0V
L N FG
~
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC
stabilized
power supply
Two-wire
terminal
Four-wire
terminal
24V
0V
24V
0V
PE
AnyWireASLINK master
[Notes on Combined Use with Four-Wire (Isolated) Terminals]
DP
DN
24V
0V
LG
24V
0V
L N FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC
stabilized
power
supply
Two-wire
terminal
DP
DN
Two-wire
terminal
DP
DN
Two-wire
terminal
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
24V
0V
24V
0V
PE
AnyWireASLINK master
24V
0V
L
N
FG
~
24V DC
stabilized
power supply
ANF-01
24V
0V
24V
0V
PE
DP
DN
24V
0V
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
A
B
General-purpose
power supply filter
(Use if necessary)
ASLINK filter
ANF-01
MAX 5A/24V DC
Filter of COSEL Co., Ltd.
EAC-06-472
MAX 6A/24V DC
Model
Type
Allowable power current
■
Filter allowable power current
Insert the "ASLINK filter [Type ANF-01]" regardless of
installation method and distance when complying with CE Standard.
General-purpose
power supply filter
(Use if necessary)
General-purpose
power supply filter
(Use if necessary)
POWER IN
SLAVE
(The figure is an explanatory schematic.
Adjust the actual terminal layout to meet each device.)
If any of the side-by-side lines of DP, DN, 24V, or 0V exceeds the total length of
50m in a power supply system to be supplied, serially connect the "ASLINK filter
[Type ANF-01]" or a "filter of COSEL Co., Ltd. [Type EAC-06-472]" to 24V and 0V
in the starting position of the side-by-side lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission
signals, and stabilize the signals.
Insert a filter whether using a master power supply for the entire system or using a
local power supply.
If any of the side-by-side lines
of DP, DN, 24V, or 0V exceeds
the total length of 50m
If (A+B) of the side-by-side
lines of DP, DN, 24V, or 0V
exceeds the total length of 50m
If any of the side-by-side lines
of DP, DN, 24V, or 0V exceeds
the total length of 50m