EN
113
PARAMETERS
Parameters Significance
Range
Standard setting
0
Temperature drop for return water Th1 in hot tap water mode
1–10 °C
5 °C
1
Temperature drop for return water Th2 in heating mode
1–10 °C
2 °C
2
Temperature drop for return water Th3 in cooling mode
1–10 °C
2 °C
3
Operation according to the heating curve
0-OFF. 1-ON
0
4
Selection of the heating curve
1–15
7
5
Correction value for the set point temperature according to the heating curve
- 2.- 1. 0. 1. 2 °C
0
6
Highest water temperature in the tank
70–90 °C
75 °C
7
Automatic temperature increase (hygiene mode)
0-NO; 1-YES
0
8
Outdoor temperature at which heating starts
-9–19 °C
18 °C
9
Outdoor temperature at which heating starts
20–53 °C
20 °C
10
Activation temperature for freeze protection for solar energy system
-9–10 °C
5 °C
11
Detection interval for auxiliary heater
15–90 min
15 min
12
Temperature drop for return water Th4 for solar energy system
3–15 °C
5 °C
13
Activation temperature for freeze protection for water tank
5–10 °C
8 °C
14
Frost protection for solar energy system
0-NO; 1-YES
15
Highest permitted temperature for water in the solar energy system tank
50–70 °C
16
Highest permitted temperature for water in the solar panel
100–120 °C
17
Emergency stop temperature for overheating of the solar energy system
120–130 °C
Operating mode according to curve
Relates to parameters 3, 4, and 5.
• When operations according to the heating curve are enabled
(parameter 3 = 1), the set point temperature in heating
mode, hot tap water + heating mode as well as mode hot
tap water + auto are controlled as a function of the current
outdoor temperature. A higher outdoor temperature gives a
lower set point temperature in heating mode and vice versa.
• The highest set point temperature for heating is 50°C.
• Use parameter 4 to set the required heating curve. There is a
total of 15 possible curves.
• The diagrams denote the highest set point temperature for
each curve
FIG. 34
FIG. 35
FIG. 36
• Parameter 5 is used to change the set point temperature set
in accordance with the selected heating curve. The actual set
point temperature will then be the set point temperature
according to the heating curve + the correction value from
parameter 5.
Example
• Parameter 3 is set to 1, operations according the heating
curve is enabled. The set point temperature for heating is
adjusted according to the heating curve, as a function of the
current outdoor temperature.
• Set parameter 4 (heating curve) to 9, set parameter 5
(correction value) to 2.
• Profit
– When the outdoor temperature is -12 °C the set point
temperature for heating is (50 + 2) °C.
– When the outdoor temperature is 0 °C the set point
temperature for heating is (40 + 2) °C.
– When the outdoor temperature is 10 °C the set point
temperature for heating is (32 + 2) °C.
Parameter setting
1. When the heat pump is in standby mode or working, press
and hold SET and
O
for 5 seconds to check the parameter
setting.
2. Press or to check the parameter values in sequence.
3. Press SET. The parameter value flashes. Press or to
increase or decrease the parameter value.
Summary of Contents for 416121
Page 3: ...1 2 1 1 1 2 2 7 3 4 5 6...
Page 4: ...4 5 6 3 1 2 3 4 5 6 12 7 8 9 11 10...
Page 5: ...4 2 5 2 1 5 3 3 3 5 6 4 2 5 2 1 3 3 3 7 8...
Page 6: ...1 6 4 2 3 1 4 2 5 3 9 10...
Page 7: ...11 12 14 13 1 2...
Page 8: ...18 15 17 16 1 3 2 4 5 6 6 1 1 2 3 4 5...
Page 9: ...19 20 21 1 2...
Page 10: ...22 24 23...
Page 11: ...25 26...
Page 12: ...29 28 27 30 31 T6 12 m 12 m T6 T6 T6...
Page 13: ...32 33 A B C D E F...
Page 15: ...36 38 37 50 C 11 12 13 14 15 SET TEMP Temp Max temp...
Page 16: ...39 40 41 A B...
Page 17: ...A B 42 43...