background image

8

WARNING: The electronic test button 
provides a full test of the unit’s functionality  
DO NOT try to test the alarm with a naked 
flame as this may present a potential fire 
hazard in itself and contaminate the alarm 

Alarm Warning Sounds

     

1 SEC 

   

Full smoke alarm with flashing LED 

  

45 SEC 

 

One beep every 45 seconds indicates low 
batteries  

    

45 SEC 

 

Two beeps every 45 seconds indicates a 
fault  

  

12 SEC 

One beep every 12 seconds indicates that 
the test button is jammed on  

ALARM  PAUSE

Abnormal air conditions may cause the 
highly sensitive smoke alarm to give 
a ‘false’ alarm  Do not disconnect the 
batteries  If no fire is apparent, ventilate 
the room and operate the ‘Alarm Pause’ 
feature by pressing the test button 

TROUBLESHOOTING

Problem

Solution

Your smoke alarm 
does not sound during 
testing

•  If testing immediately after first activating the alarm or replacing the batteries, 

you should allow a few seconds for the alarm to settle before testing 

•  Make sure you push the centre of the test button firmly 

•  If the alarm has been recently fitted and it still fails to self test 

then contact Technical Support on:

 0800 141 2561

 or e-mail: 

 

[email protected]

 

The operating light 
remains steadily on 
or off

•  Inspect for obvious damage 

•  Check the unit contains the recommended battery type and that it is properly 

connected 

•  If in doubt, contact Technical Support on:

 0800 141 2561

 or e-mail: 

 

[email protected]

 

 The alarm beeps twice 
every 45 seconds

•  This indicates a fault with the alarm 

•  Inspect for obvious damage 

•  Check the unit contains the recommended battery type and that it is properly 

connected 

•  If in doubt, contact Technical Support on:

 0800 141 2561

 or e-mail: 

 

[email protected]

 

Your smoke alarm 
beeps every 45 seconds

•  This indicates that the battery is low and needs replacing  

•  Refer to the ‘Battery Replacement’ section of this manual  

WARNING:

 If there is any question as to 

the cause of an alarm, always assume that 
this is due to an actual fire and follow your 
fire emergency plans  Do not assume the 
alarm is a nuisance alarm 

BATTERY 

REPLACEMENT

Your alarm requires two AAA (LR03) 
alkaline batteries  Under normal use, the 
batteries should last approximately one 
year 
•  Low Battery Warning - alarm beeps 

every 45 seconds for up to 30 days 
when the battery needs replacing 

•  Low Battery Waming Silence - low 

battery warnings often start at night  
Silence the audible warning for ten 
hours by pressing the test button, 
thus avoiding removing the batteries  
Change the batteries the following 
day  The red LED flashes twice every 
45 seconds to remind you that the low 
battery warning has been silenced 

IMPORTANT: Test alarm using test facility 
whenever batteries are replaced 

Summary of Contents for SA700-AE-UK

Page 1: ...1 y mar Title Description User Manual Material 60GSM Wood Free Paper Used On Used For SA700 AE UK Size W 120mm H 120mm Supplier PACE Print Colours CMYK User Manual Optical Smoke Alarm www angeleye com SA700 AE UK ...

Page 2: ...echnicalsupport sprue com Web www sprue com Sprue Safety Products Ltd Vanguard Centre Coventry CV4 7EZ UK A Sprue Brand GN3563R1 SA700 AE UK Optical Smoke Alarm 0086 0086 CPR 597993 Smoke alarm devices EN 14604 2005 DOP 13 02 14 BS EN 14604 2005 Licence No KM597992 ...

Page 3: ...arm Pause 8 Note This user manual is also available in large text and other formats Please email technicalsupport sprue com or call 0800 141 2561 for further information CONTENTS Battery Replacement 8 Troubleshooting 9 Maintenance 10 Disposal 10 Warranty 11 ...

Page 4: ...ew build properties In this type of property the building regulations require alarms to be interlinked You can obtain further information from your local fire service or building control department at your local council offices These sources generally provide advice on new builds or projects that require planning permission Your smoke alarm typically meets the minimum requirements for family livin...

Page 5: ...y hallways and landings Install smoke alarms in circulation areas at a distance no greater than 7 5m from the farthest wall no greater than 7 5m from a door to any room in which a fire might start and no greater than 7 5m from the next smoke alarm If it is necessary to place a smoke alarm on a wall always locate the detection element of the alarm 150mm to 300mm 6 to 12 inches below the ceiling and...

Page 6: ...oke alarm is to be fitted it should be located horizontally on the ceiling either in the living room or the hall but not in the proximity of either kitchen or bathroom 2 Additional alarms can be fitted in bedrooms 3 DO NOT locate alarm close to exhaust fans or air conditioning INSTALLATION 4 Separate the alarm from the mounting plate This may require you to turn the alarm clockwise while holding t...

Page 7: ... 7 Line up the arrow on the back of the alarm with the arrow inside the base plate and inset the alarm Once the alarm is inside the base plate twist it anti clockwise to lock it into place 8 Test the alarm ALARM TEST 1 Press and release the test button to test alarm The alarm should sound three times 2 After testing check that the red light flashes approximately every 40 seconds 3 Test the alarm o...

Page 8: ...e feature by pressing the test button WARNING If there is any question as to the cause of an alarm always assume that this is due to an actual fire and follow your fire emergency plans Do not assume the alarm is a nuisance alarm BATTERY REPLACEMENT Your alarm requires two AAA LR03 alkaline batteries Under normal use the batteries should last approximately one year Low Battery Warning alarm beeps e...

Page 9: ...emains steadily on or off Inspect for obvious damage Check the unit contains the recommended battery type and that it is properly connected If in doubt contact Technical Support on 0800 141 2561 or e mail technicalsupport sprue com The alarm beeps twice every 45 seconds This indicates a fault with the alarm Inspect for obvious damage Check the unit contains the recommended battery type and that it...

Page 10: ...aint the smoke alarm as this may block the openings and prevent smoke from entering the sensor Storage in low humidity and certain transportation conditions may cause electrostatic charges to build up in the alarm system housing Although harmless they may increase the length of time that the horn sounds upon battery insertion or test button operation The condition may be cleared by gently wiping t...

Page 11: ...om the date of original retail purchase and is not transferable Proof of purchase is required This warranty does not cover damage resulting from accident misuse disassembly abuse or lack of reasonable care of the product or applications not in accordance with the user manual It does not cover events and conditions outside of Sprue Safety Products Ltd s control such as Acts of God fire severe weath...

Page 12: ......

Reviews: