Technical Data
17
MAXXfl o EVO
Menu
Parameter
Settings
Confi guration
6020
Set the function of extension module 1 to "Multifunction"
6030
Set Relay output QX21 module 1 to "dT controller 1 K21"
6041
Set sensor input BX22, module 1 to "Special temperature sensor 1"
General
functions
5570
Factory setting: not used
5571
Factory setting: "- 1.5
O
C" - When the temperature of the BUFFER SS300-10 tank is 0.5
O
C
lower than the temperature of the grid tank, the K21 pump is switched off
5572
Factory setting: "3.0
O
C" - When the temperature of the BUFFER SS300-10 tank is less than
2.0
O
C below the temperature of the storage tank, the K21 pump is switched on.
5573
Factory setting: "DHW sensor B3"
5574
Factory setting: "Special temperature sensor 1"
5575
Mode of action: 30 seconds - represents the minimum time that the K21 pump will be acti-
vated even if the conditions of parameter 5571 are met.
Parameter settings table (in addition to examples 1 & 2):