SECTION 3 •
INSTALLATION
22
E861
(230 Litre)
E865
(380 Litre)
E862
E860
E863
Condense
syphon
Condense pipe
to drain
ECOflo 230 & 380 LITRE FLUE SYSTEMS
The ECOflo uses a concentric flue system,
150mm
outside diameter with an inner flue of 100mm
diameter.
Flue components fit together with silicon sealing rings and
the flues are retained with sealing clamps. Each heater
can be ordered with either a horizontal or vertical flue kit.
Flue assembly instructions are also included.
Prior to installing the concentric flue system and
terminal, the following must be carried out:
1) Fit item E860 to the stainless steel exhaust outlet
connection on the appliance and ensure that the
condense connection is at the base of the tee piece.
2) Fit item E862 to the PVC air intake connection on
appliance and ensure that the open end is at the top
of the tee piece.
3) Fit item E861 or E865 (depending on the model) to
both previously fitted E860 and E862. Ensure that
both connectors are located correctly. Secure the
100mm dia. vertical section of item E861 or E865 to
heater outer casing with brackets supplied. Ensure
that internal cable is not damaged during installation.
4) Fit item E863 condense syphon to 32mm connection
at base of condense tee (E860).
5) Install 40mm OD plastic waste system from syphon
outlet to suitable drain.
A minimum downward slope of between 3mm to
6mm per 300mm length of water pipe must be
adhered to.
ECOflo_E864_manual_SEPT2012 16/10/12 11:24 Page 22