SECTION 3 •
INSTALLATION
20
VERTICAL FLUE KIT/FITTINGS PACK
– 380 LITRE MODELS
AWH PART No: B292
SUPPLIED COMPONENTS
Part Description
Part Number
Exhaust Outlet Tee c/w Condense Outlet (82500)
E860
100mm to Concentric Exhaust Pipe (75413)
E865
Air intake Tee Piece Connector (82501)
E862
Condense Syphon (87436)
E863
Horizontal Flue Terminal, 100/150mm (87990)
E236
90° Elbow c/w clamp, 100/150 (87890)
E205
Gas Cock – ¾”BSP
C498
Drain Valve – ¾”BSP
C381
Drain Valve Socket – ¾”BSP
C103
Installation, Operation and Maintenance Manual
E864
VERTICAL FLUE KIT/FITTINGS PACK
– 380 LITRE MODELS
AWH PART No: B294
SUPPLIED COMPONENTS
Part Description
Part Number
Exhaust Outlet Tee c/w Condense Outlet (82500)
E860
100mm to Concentric Exhaust Pipe (75413)
E865
Air intake Tee Piece Connector (82501)
E862
Condense Syphon (87436)
E863
Vertical Flue Terminal, 100/150mm (87969)
E866
Gas Cock – ¾”BSP
C498
Drain Valve – ¾”BSP
C381
Drain Valve Socket – ¾”BSP
C103
Installation, Operation and Maintenance Manual
E864
FLUE SYSTEMS
Optional Components for 100/150mm dia (concentric) Flue
Quantity
Flue Length
Part Description
Part Number
1
1000mm (40in)
Flue pipe with clamp
E202
1
1000mm (40in)
Cutable flue pipe with clamp
E203
1
500mm (20in)
Flue pipe with clamp
E204
1
90° Elbow
E205
1
45° Elbow
E206
1
Flat roof flashing for vertical flue terminal with adjustable cap
E207
1
Roof flashing for pitched roof to suit 150mm (6in) dia flue size
E208
1
Wall clamp 150mm (6in) dia.
E209
1
Flue condense trap
E210
1
Syphon
E211
1
Condensate trap pipe kit to syphon
E261
Model
EC230/600
EC230/700
EC230/960
EC380/740
EC380/980
EC380/1220
EC380/1400
Flue size (concentric)
mm
100/150
100/150
100/150
100/150
100/150
100/150
100/150
Max flue run – room sealed (a) m
16
16
16
16
16
16
16
Reduce flue length by 1.2m for 90° bend, 0.7m for 45° bend and 1.5m for a condensate trap.
The ventilation requirements for room sealed flue systems are given on pages 29 and 30.
ECOflo_E864_manual_SEPT2012 16/10/12 11:24 Page 20