SYSTEM SET-UP & CHECKOUT

Skip set up and proceed to 

INSTALLER TEST MODE

 on page 8 unless:

•  A Model A77 or other external control is to be installed

•  Changing the air sampling rate

1. 

Make sure the wire access cover has been snapped back onto the 
on-board control�

2. 

Plug unit in and turn power switch to ON�

3. 

The on-board control screen should display OFF�

90-1854

NOTE:

 If the display backlight is not on, the first button press (any 

button) will only turn on the backlight� Press the button a second time 
to achieve function� 

4. 

Hold the MODE button on the on-board control for 3 seconds to 
enter the Installer Set-up Menu�

5. 

Navigate through the following screens to set up the dehumidifier 
for the installed application�

   Use the UP or DOWN buttons to select items and use MODE to 

switch to the next set-up option� To exit installer set-up, all options 
must be scrolled through using the MODE button� 

6. 

After the installer set up options have been completed, DONE will 
blink for 3 seconds and the control will return to the OFF screen�

90-1854

90-1854

REMOTE CONTROL

90-1854

If not installing an A77, leave 
DISABLED and press MODE to go 
to the next screen�� 
 
 

90-1854

If installing an A77, use the UP or 
DOWN button to select ENABLED, 
then press MODE to go to the next 
screen� 
 

EXTERNAL CONTROL

90-1854

If using the dehumidifier on-board 
control, leave DISABLED and press 
MODE to go to the next screen� 
 
 

90-1854

If using a Model 8800 series 
thermostat or alternate control as 
an external control, use the UP or 
DOWN button to select ENABLED, 
then press MODE to go to the next 
screen�

7

Summary of Contents for A100F

Page 1: ...IER FOR INSTALLATION 3 LOCATION CONSIDERATIONS 3 DRAIN INSTALLATION 4 Leveling 5 Condensate Pan Condensate Pump and Float Switch 5 MODEL A77 REMOTE CONTROL AND WIRING 6 Alternate External Controls 6 S...

Page 2: ...property damage or injury Read instructions before installation service or maintenance 3 Do not use in pool applications Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on...

Page 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Page 4: ...result in air lock NOTE PTFE thread seal tape is recommended for the threaded connection and hand tighten only If hard pipe is used PVC primer and cement is recommended for the slip fit connection Re...

Page 5: ...the condensate pan remove the factory installed jumper wire between the Float Switch terminals on the control and wire the float switch to the dehumidifier as shown in FIGURE 4 Overflow safety switche...

Page 6: ...rt up instructions The Model A77 will measure the relative humidity and turn the dehumidifier on and off to control the humidity level to the desired setting The humidity setting can be adjusted from...

Page 7: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Page 8: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Page 9: ...tting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the System Set...

Page 10: ...r 3 seconds to clear the service message 90 1854 MAINTENANCE CLEAN OR REPLACE THE AIR FILTER After initial installation the air filter should be checked and cleaned every 6 months The CLEAN FILTER ser...

Page 11: ...p and gently lifting the cover up and out of the drain pan 6 Clean the drain insert with warm water and mild detergent solution REINSTALLING THE DRAIN INSERT 1 Reinstall the drain insert by inserting...

Page 12: ...ture while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Failure 1 Check t...

Page 13: ...s installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier air filter and replace if necessary Check for blocked duct work Inlet...

Page 14: ...Deh 5882 6 Fan 100pt Deh with 12MFD Capacitor 5886 7 Wire Harness Power Deh 5884 8 Sensor Low Temperature Deh 5455 No Part Description Part No 9 Sensor High Temperature Deh 5456 10 Capacitor Run 50 F...

Page 15: ...IABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLU...

Page 16: ...anden com P O Box 1467 Madison WI 53701 1467 800 972 3710 F 608 257 4357 Printed in USA 2021 Anden A Quality brand from Research Products Corporation 10015567 B2209250A 1 21...