CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
A condensate pan is recommended when locating in or above a finished
space or suspending over the canopy� Adhere to local codes regarding
draining of the condensate pan� If a condensate pump is needed, install
it in the condensate pan as well�
Install a condensate overflow safety switch (i�e� float switch) in the
condensate pan, remove the factory installed jumper wire between
the Float Switch terminals on the control and wire the float switch to
the dehumidifier as shown in
FIGURE 4
� Overflow safety switches on
condensate pumps can be wired to the Float Switch terminals in a
similar fashion�
FL
OAT
Swit
ch
DH
DH
NORMALLY CLOSED
FLOAT SWITCH
90-1857
FIGURE 4
– FLOAT SWITCH WIRING
LEVELING
A level surface is required to ensure proper drainage from the dehumidifier� Refer to top mounted bubble level and adjust position until bubble is
within the outer circle�
5