AIR SAMPLING

90-1854

Use the UP or DOWN button to 
adjust how frequently the 
dehumidifier samples the air to 
determine whether or not to 
dehumidify� Fewer minutes means 
the dehumidifier will sample more 

frequently to minimize humidity swings, but increases cost to operate 
due to more frequent fan operation� Press MODE when done to move to 
the next screen�

RH OFFSET

90-1854

An offset can be applied to the 
on-board humidity reading to 
avoid discrepancies with other 
humidity measuring devices in the 
home� Use the UP or DOWN 
button to select an offset from -5% 
to 5%� Press MODE to exit the 
installer set-up screens�

INSTALLER TEST MODE

If everything is properly wired, the dehumidifier and all of the 
wired components will turn on and off during Installer Test 
Mode to demonstrate that all are properly operating� Installer 
Test Mode lasts for four (4) minutes� If the ON/OFF button is 
pressed during test mode, the dehumidifier will exit Installer 
Test Mode and return to the OFF screen�

DEHUMIDIFICATION ONLY

90-1854

If the dehumidifier is not 
already OFF, press the ON/
OFF button to turn it off� 
 
 
 

90-1854

Press and hold the ON/
OFF button and MODE 
buttons for 3 seconds� The 
measured humidity, AIR 
SAMPLING and TEST will 
show on the display� 

90-1854

After three (3) minutes the 
dehumidifier compressor 
will turn on and 
DEHUMIDIFYING will 
replace AIR SAMPLING on 
the control screen� 

90-1854

After one minute of 
compressor operation, all 
outputs will turn off and 
DONE will blink for 3 
seconds and then return to 
the OFF screen� 

90-1854

8

Summary of Contents for A100F

Page 1: ...IER FOR INSTALLATION 3 LOCATION CONSIDERATIONS 3 DRAIN INSTALLATION 4 Leveling 5 Condensate Pan Condensate Pump and Float Switch 5 MODEL A77 REMOTE CONTROL AND WIRING 6 Alternate External Controls 6 S...

Page 2: ...property damage or injury Read instructions before installation service or maintenance 3 Do not use in pool applications Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on...

Page 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Page 4: ...result in air lock NOTE PTFE thread seal tape is recommended for the threaded connection and hand tighten only If hard pipe is used PVC primer and cement is recommended for the slip fit connection Re...

Page 5: ...the condensate pan remove the factory installed jumper wire between the Float Switch terminals on the control and wire the float switch to the dehumidifier as shown in FIGURE 4 Overflow safety switche...

Page 6: ...rt up instructions The Model A77 will measure the relative humidity and turn the dehumidifier on and off to control the humidity level to the desired setting The humidity setting can be adjusted from...

Page 7: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Page 8: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Page 9: ...tting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the System Set...

Page 10: ...r 3 seconds to clear the service message 90 1854 MAINTENANCE CLEAN OR REPLACE THE AIR FILTER After initial installation the air filter should be checked and cleaned every 6 months The CLEAN FILTER ser...

Page 11: ...p and gently lifting the cover up and out of the drain pan 6 Clean the drain insert with warm water and mild detergent solution REINSTALLING THE DRAIN INSERT 1 Reinstall the drain insert by inserting...

Page 12: ...ture while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Failure 1 Check t...

Page 13: ...s installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier air filter and replace if necessary Check for blocked duct work Inlet...

Page 14: ...Deh 5882 6 Fan 100pt Deh with 12MFD Capacitor 5886 7 Wire Harness Power Deh 5884 8 Sensor Low Temperature Deh 5455 No Part Description Part No 9 Sensor High Temperature Deh 5456 10 Capacitor Run 50 F...

Page 15: ...IABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLU...

Page 16: ...anden com P O Box 1467 Madison WI 53701 1467 800 972 3710 F 608 257 4357 Printed in USA 2021 Anden A Quality brand from Research Products Corporation 10015567 B2209250A 1 21...

Reviews: