11

Dry Contact Relay

The charger is fitted with a dry contact relay to indicate output failure to a monitoring system. 

To use the dry contact output fail relay you must connect a 9-pin D connector to the unit. You 

must use pins one and six as is indicated on the remote connector diagram.

The relay is factory preset to fail in the closed position when the low output LED and buzzer 

come on. If you wish to have the relay fail in the open position when the low output LED and 

buzzer come on, you must take the cover off the unit and move the jumper to the other posi-

tion on J11. J11 is located next to the relay.

To change the position of the jumper, first turn the unit off and disconnect the unit from both 

the power and batteries. Next, turn the unit on for 30 seconds to discharge the capacitors, 

and then turn it off again. Turn the unit upside down and remove the four screws. Remove 

the base plate and locate J11. It will be next to the relay as is shown in the above diagram. 

Simply move the jumper to the desired position as is shown in the above diagram. Replace the 

base plate and re-install the four screws. Reconnect the unit to the power and batteries.

Field Conversion from 110Vac to 220Vac Operation

This unit may be converted from 110Vac operation to 220Vac operation. Please contact the 

dealer or manufacturer if you wish to convert your unit. (Attempting to do this conversion 

yourself, will void the warranty!)

BATTERY TEMPERATURE SENSORS

Up to 2 battery temperature sensors can be connected to the charger to allow temperature 

compensation of the battery charging voltage (1 is supplied with the unit). If only the 1 sensor 

is used, it MUST be plugged into the ‘BATT 1’ connection on the rear of the unit. If no sensor 

is used, the charger will default to standard output voltage.

For installation instructions of the temperature sensor, please see the section entitled 

Remote Battery Temperature Sensor Installation

Summary of Contents for BCA310MS

Page 1: ...Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inver...

Page 2: ...Copyright 2005 2014 Analytic Systems Ware 1993 Ltd...

Page 3: ...RISK OF EXPLOSIVE GASES i WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EA...

Page 4: ...rer This helps purge excessive gas from cells Do not overfill For a battery without cell caps carefully follow manufacturer s recharging instructions 3 BATTERY CHARGER LOCATION i Never place battery c...

Page 5: ...l supply the DC load as well as charge float the battery In case the AC power fails or if the charger stops working the battery will automatically power the DC load As soon as the AC power to the char...

Page 6: ...AGC 10 AGC10 Output Crowbar 16 0 0 5 V 32 0 1 0 V 42 7 1 3 V 63 5 0 5V Temperature Compensation Coefficient 30mV o C 60mV o C 80mV o C 120mV o C General Efficiency 75 maximum output Stages 2 or 3 Tem...

Page 7: ...All connections should be made inside an appropriate junction box The maximum current draw from the 110 VAC supply is 5 2 amps so a 7 amp circuit breaker should be used in the circuit panel For a 220...

Page 8: ...illuminate When the unit is first turned on it will charge the batteries at maximum current and the charging light will be on After a period of time which may be minutes to hours the batteries will r...

Page 9: ...is the fastest charger It charges the battery at a constant current until the battery voltage reaches a slightly elevated level The battery is maintained at this voltage while the charging current di...

Page 10: ...n after all the loads have been disconnected the unit is defective and must be returned to the factory or an authorized service center for repair If the unit will not turn on at all check the input fu...

Page 11: ...ve the four screws Remove the base plate and locate J11 It will be next to the relay as is shown in the above diagram Simply move the jumper to the desired position as is shown in the above diagram Re...

Page 12: ...hich are undercharged will be brought up to full charge An Equalize cycle should be done once every 2 3 months or whenever battery capacity appears to be diminished The Equal ize Option also includes...

Page 13: ...the battery so as to prevent it from losing contact Battery Charger Temperature Compensation The charger is calibrated with the sensor input preset to 77 degrees 25 degrees C For example for a 12V bat...

Page 14: ...p Components Conformal Dipping and RTV Compound Option w Wide Temperature Operation 40 to 55 C incl Option SM High Voltage Protection on the DC Input Side Option d Paralleling Diodes Option FI Forklif...

Page 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed o...

Page 16: ...Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage...

Reviews: