6
Specifications
Input Voltages
Nominal (ip)
110
220
Actual (Vac)
90 - 130
180 - 260
Frequency (Hz)
45 - 65
Input Amps (max)
5.2
2.6
Input Fuse (slow blow)
MDA-7
MDA-4
Output Voltages
Nominal (op)
12
24
32
48
Float (Vdc)
13.6 ± 0.05
27.2 ± 0.05
36.3 ± 0.05
54.4 ± 0.05
Absorption Voltage (Vdc)
14.4
28.8
38.4
57.6
Charging Amps
20
10
7.5
5A
Absorption to Float
3.0 Amps
1.5 Amps
1.13 Amps
0.75A
Battery Banks
1, 2 or 3
Battery Size (Amp Hours)*
80 – 120
40 - 60
30 – 45
20-35
Output Adjust
± 1.0 Volts
Output Fuses
AGC 25
AGC 15
AGC 10
AGC10
Output Crowbar
16.0 ± 0.5 V
32.0 ± 1.0 V
42.7 ± 1.3 V
63.5 ± 0.5V
Temperature Compensation Coefficient -30mV / o C
-60mV / o C
-80mV / o C
-120mV / o C
General
Efficiency
> 75 % @ maximum output
Stages
2 or 3
Temp. Range
-40°C to +50°C @ maximum output
Isolation
Input-Case & Input-Output 1500 VDC, Output-Case 500 VDC
Length
9.6 in / 24.4 cm
Width
8.2 in / 20.8 cm
Height
3.5 in / 6.4 cm
Clearance
1 Inch (2.5 cm) all around
Material
Marine Grade Aluminum
Finish
Black Powder Epoxy
Fastenings
18-8 Stainless
Weight
7.0 lb / 3.2 kg
Safety
ABS 11-HS794404A-PDA
* Specifications subject to change without notice.